Our Products
Business Management Consultants
2 Products availableGas Plants
2 Products availableFire Fighting & Protection
2 Products availableIrrigation Equipment & Systems
1 Products availableTextile Processing Machinery
1 Products availableLeak Detectors
1 Products availableSigns
1 Products availableBattery Powered Torches
1 Products availableSteel & Steel Products
1 Products availableWe are leaders in the market for providing best range of VESDA System, Inergen and Gas Fire Suppression
Gas Suppression Systems FM-200 (HFC-227EA) is a reliable solution based on HFC 227ea, an extinguishing agent known around the world. Built on 42-bar technology, these Gas Suppression Systems are efficient and space-saving. Whether for the valuable systems, data, people or the working environment, this Gas Suppression System provides optimum protection in case of fire and helps ensuring business continuity. The extinguishing agent of this Gas Suppression System is very effective and works at low extinguishing concentrations to protect people and assets. The extinguishing agent is chemically inert and has low electric conductivity. This Gas Suppression Systems provides ideal protection especially for areas with electrical and electronic risks of fire. Extinguishing without leaving any residue and without risking of corrosion is found in this Gas Suppression System- for example a smoldering fire in electrical switching rooms, telecommunication systems, data centers or server rooms can be checked before it spreads.
Features
Technical Specifications
Listings/Approvals
Fire Hydrant System that we provide is used to protect entire plant/building/risk. Fire Hydrant System that we offer comprises of network of underground & above ground piping throughout the protected area. This piping network pressurized with water using pumps is connected to reliable source of water. We can provide Fire Hydrant System at competitive prices.
Our Fire Hydrant System Consist Of :
We provide a one-stop solution to the problem of power supply failure in household premises and commercial buildings. These Battery Operated Emergency Lights are battery operating Emergency Light, which enlighten through burning one or more incandescent bulbs or one or more clusters of high-intensity light emitting diodes. The range of Battery Operated Emergency Light, which we offer, has excellent battery backup with self –luminous signs. These Battery Operated Emergency Lights also have chemical lighting elements and countless options for cool-burning LEDs. Further, customization on these Battery Operated Emergency Lights is also done. Features Of Emergency light :
We are engaged in providing VESDA Systems that are air sampling based high sensitivity smoke detection systems. VESDA (very early smoke detection apparatus) comprises of an aspirated smoke detector and a network of PVC piping, which is capable of detecting fires at a very early incipient stage. These systems are deployed for mission critical areas like data centers, control rooms and data processing areas, as the first line of defense against fire situations. These are available at market leading prices. Why Our VESDA System?
A Fire Alarm System, which we offer, is an active fire protection system that detects fire or the effects of fire, and as a result, provides one or more of the following
The detectors senses cause of fire and then give the signal through the alarm system. Fire Alarm Systems can include Alarm Initiating Devices, Alarm Notification Appliances, Control Units, Fire Safety Control Devices, Annunciator, Power Supplies and Wiring.
Special Detectors : Smoke & Heat Combined Detector, Linear Heat sensing cable, Laser Detector, Beam Detector, UV-Detector & IR-Detector
We provide a one-stop solution to the problem of power supply failure in household premises and commercial buildings. These Battery Operated Emergency Lights are battery operating Emergency Light, which enlighten through burning one or more incandescent bulbs or one or more clusters of high-intensity light emitting diodes. The range of Battery Operated Emergency Light, which we offer, has excellent battery backup with self –luminous signs. These Battery Operated Emergency Lights also have chemical lighting elements and countless options for cool-burning LEDs. Further, customization on these Battery Operated Emergency Lights is also done. Features Of Emergency light :
We offer our clients high quality Gas Leak Detector, which is known for features like high sensitivity and reliable performance. The Gas Leak Detector, offered by us, has a compact size and 220V power supply due to which, it provides a long stability and long functional life. This Gas Leak Detector also has an in-built transmitter to send immediately an alarm signal, and also has a built in battery backup. Why Our Gas Leak Detector?
We offer high quality Night Glow Signages, giving appropriate directions and safety signals to the users to prevent various accidental cases and damages. These Night Glow Signages are made of high quality raw materials and constructed by advanced technologies. These Night Glow Signages are used in various public and commercial places to avoid many dangerous incidents. Used In :
We offer the Hose Reel System that provides immediate and continuous flow of water when the hose is deployed. The Hose Reel System provided by us is also equipped with heavy duty all-purpose ball valves and nozzles. These Hose Reel Systems are treated as one of the safest and efficient equipment, which can be made available as per the requirements of the customers. To support the fire hoses, the fire reels are made, which keep them tidy so that they can assemble for instant requirements as an aid for suppressing unexpected fires.
NAF® S 125 is a UL Recognized and US EPA SNAP Listed gaseous extinguishing agent. NAF® S 125 Engineered Systems are UL Listed.
NAF® S 125 is suitable for use in rooms, vaults, enclosed machines, containers, storage areas and wherever fixed enclosures are present. It is an electrically non-conductive media, it can therefore be used to protect electronic and delicate equipment. After discharge NAF® S 125 does not require the clean-up of the protected enclosure, making it extremely useful in applications where damage by other extinguishing methods would be prohibitive.
NAF® S 125 has a low order of toxicity. At typical design concentrations it can be safely used to protect normally occupied areas.
The NAF S 125® formulation includes a patented additive that reduces the levels of decomposition by-products normally generated by halocarbons during extinguishment and enhances extinguishing performance (inter alia US Patent No. 6, 402, 975 and EU Patent No. 630, 278).
By weight NAF® S 125 requires the lowest concentration, making NAF® S 125 the most cost effective clean agent solution available in the market today.
They are available in 180º and 360º coverage that is suitable for total flooding systems in occupied areas. This Gas Suppression System protects areas such as computers, archives, electrical and telecommunications equipment, Server Room/Data Center, Hospitals, Petrochemical, Offshore, Airport, Laboratories, Paint Booths, etc. The typical design concentration of this Gas Suppression System is 8%, with a discharge time of 10 seconds in accordance with the UL 2166 regulations.
Discharge is via valves that have been completely designed by manufacturer and certified by the top independent agencies. This gas suppression system offers great flexibility of adaptation to all actuation systems currently on the market, and even allows combinations of several of these. This gas suppression system design incorporates elements that protect against accidental activation due to micro-seepage. All of the valves are registered through the Ministry of Industry and thus comply with an obligatory standard. The NAF S125 extinguishing systems include discharge nozzles especially designed to maximize the properties of the extinguishing agent. They are available in 180º and 360º coverage.
Main benefits :
Certificates :
Physical Properties
| Composition | HFC-125 + 0.15% of Limonene |
|---|---|
| Molecular weight | 120.0 |
| Boiling point @ 1.013 bar | -48.3°C |
| Density of the liquid @ 25°C | 1189.7 kg/m³ |
| Critical temperature | 339.45 K |
| Critical pressure | 3595 Kpa |
| Vapor pressure @ 20°C | 12.09 bar |
| Relative electrical resistance @ 1 atm. 21°C (N2=1.0) | 0.955 |
NFPA 2001 Edition 2012
| Design concentration for Class A Fires | 8.7% (by volume) |
|---|---|
| Flooding factor for Class A Fires | 0.484 kg/m³ |
| Design concentration for Class C Fires | 9% (by volume) |
| Flooding factor for Class C Fires | 0.502 kg/m³ |
ISO 14520 Edition 2006
| Design concentration for Class A/C Fires | 8.7% (by volume) |
|---|---|
| Flooding factor for Class A/C Fires | 0.484 kg/m³ |
| PBPK (5 minutes exposure) | 11.5% |
| Ozone Depletion Potential (ODP) | 0 |
| Global Warming potential (GWP) | 2800 |