Delhi, India
Our Products
We offer a complete product range of Three Phase Input Three Phase Output Online UPS, Three Phase Input Single Phase Output Online UPS and single phase online ups
The HF Series includes the 10KVA to 300 KVA (3 phase input, 3 phase output) double conversion On-Line UPS with an isolation transformer. The Load is supplied continuously by the inverter with clean, stabilized and regulated sine wave output power. Input & Output filters protect the load from Voltage fluctuation and surges. Its applications include mission critical load like IT, Call Centres, Hospitals, CNC machines etc. Thanks to state-of-the-art microprocessor based high frequency PWM technology.
Salient Featurs :
Applications :
Specifications
Input Voltage | Three Phase |
Voltage range | 340 to 460V |
Frequency | 45-55 Hz |
Inverter | |
Output Wave Form | Pure Sine Wave |
Output voltage | 415V/400V/380V (adjustable) |
Output voltage regulation | +/- 1% |
Output Frequency | 50Hz +/- 0.01% |
Output Isolation | Galvanic Isolation |
Power Factor | 0.8 to unity (0.9 optional upto 30KVA with extra charges) |
THD | Less than 3% |
Technology | Micro controller based Hi Freq. PWM |
Overload Capacity | 110% for 10 Min. |
Crest Factor | 0.17 |
Transient Recovery | Within 3 cycle |
Battery Charger | |
Charger Type | Constant Voltage Constant Current |
Charging Mode | Trickle, Float & Boost |
Operating Conditions | |
Operating Temperature | 0-45oC |
Humidity | 90% Non Condensing |
Noise Level | Less than 45dB |
Response Time | |
Transfer Time | 0 ms |
Dimensions (mm) (L x W x H) | |
10 - 30KVA | 895 x 460 x 910 |
40 – 60KVA | 1150 x 505 x 1040 |
80, 100, 120KVA | 1700 x 690 x 1400 |
160 – 300KVA | 1910 x 765 x 1495 |
Note : Due to continuous product development, specifications are subject to change without prior notice.
Ability to Work with all Loads - An obvious choice for IT applications, the heavy duty design of the HF Series also works equally well with other loads such as motor driven loads, medical equipment, communication products which are often damaged by inferior UPSs with step wave or square Wave output. The rugged Nexus HF Series Online UPS systems are designed to perform in the most hostile of Indian Power conditions.
Generator Compatible : As a series designed for Indian conditions, the HF Series UPSs also score over most other systems in the market, affording high compatibility with most types of generators.
Hot Stand-by Mode : In rare instances where the primary UPS system goes out of order the standby UPS instantly takes on the connected load without transferring to bypass. This configuration is available on selected models at an additional cost.
Features :
Application :
Specifications
Input Voltage | Three Phase |
Voltage range | 340 to 460V |
Frequency | 45-55 Hz |
Inverter | |
Output Wave Form | Pure Sine Wave |
Output voltage | 220V |
Output voltage regulation | +/- 1% |
Output Frequency | 50Hz +/- 0.01% |
Output Isolation | Galvanic Isolation |
Power Factor | 0.8 to unity (0.9 optional upto 30KVA with extra charges) |
THD | Less than 3% |
Technology | Micro controller based Hi Freq. PWM |
Overload Capacity | 110% for 10 Min. |
Crest Factor | 0.17 |
Transient Recovery | Within 3 cycle |
Battery Charger | |
Charger Type | Constant Voltage Constant Current |
Charging Mode | Trickle, Float & Boost |
Operating Conditions | |
Operating Temperature | 0-45oC |
Humidity | 90% Non Condensing |
Noise Level | Less than 45dB |
Response Time | |
Transfer Time | 0 ms |
Dimensions (mm) (L x W x H) | |
10 - 30KVA | 615 x 460 x 910 |
40KVA | 895 x 460 x 910 |
Note : Due to continuous product development, specifications are subject to change without prior notice.
Latest State of Art HF series Ups - Nexus HF Series is latest state of the art Micro controller based High Frequency PWM Technology UPS using IGBT's for higher efficiency and greater reliability. The HF Series UPS provide pure sine wave output and is designed for wide input voltage range from 170V to 270V. NEXUS On-Line HF series UPS isolates the critical load from any disturbance by providing complete protection against spike, surges, brown outs, black outs, voltage and frequency variation.
Details : Ability to Work with all Loads With pure sine wave output, Nexus On-Line HF Series UPSs can not only work with Computer applications but can also work with other loads such as motor driven loads, medical equipment, communication products which are often damaged by UPS with step wave or square Wave output.
Salient Features :
Applications :
Specifications
Input Voltage | Single Phase |
Voltage range | 170 to 270V |
Frequency | 45-55 Hz |
Inverter | |
Output Wave Form | Pure Sine Wave |
Output voltage | 220V |
Output voltage regulation | +/- 1% |
Output Frequency | 50Hz +/- 0.01% |
Output Isolation | Galvanic Isolation |
Power Factor | 0.8 to unity (0.9 optional with extra charges) |
THD | Less than 3% |
Technology | Micro controller based Hi Freq. PWM |
Overload Capacity | 110% for 10 Min. |
Crest Factor | 0.17 |
Transient Recovery | Within 3 cycle |
Battery Charger | |
Charger Type | Constant Voltage Constant Current |
Charging Mode | Trickle, Float & Boost |
Operating Conditions | |
Operating Temperature | 0-45oC |
Humidity | 90% Non Condensing |
Noise Level | Less than 45dB |
Response Time | |
Transfer Time | 0 ms |
Dimensions (L x W x H) | |
1.0 - 6.0KVA | 525mm x 275mm x 515mm |
7.5KVA - 10KVA | 520mm x 345mm x 585mm |
Note : Due to continuous product development, specifications are subject to change without prior notice.