Leading Manufacturer, Supplier & Retailer of Contact Resistance Meter.

Contact Resistance Meter

  • Number Of Flower Meter
  • Application Measuring Static Contact Resistance In Circuit Breakers
  • Method Kelvin's 4-wire Method
  • Source Built-in Continuous DC Source Up To 200A
  • Range Micro-ohm Range
  • Measurement Millivolt Drop Across Contacts
  • Mobility Mounted On A Trolley For Easy Mobility
Measuring static contact resistance is crucial for assessing the health and functionality of a circuit breakers main contacts. Poor contact conditions can lead to arcing and single phasing, often resulting from oxide deposits and moisture absorption, which increase contact resistance. This, in turn, causes I2R losses due to hot-spotting when the circuit breaker closes.The MVT Contact Resistance Meter employs Kelvins 4-wire method to measure the static resistance of circuit breaker main contacts precisely. It features a built-in continuous DC source of up to 200A and conducts resistance measurements in the micro-ohm range by assessing the millivolt drop across the contacts.Mounted on a trolley for easy mobility on the shop floor, the MVT is suitable for evaluating contact resistances of vacuum circuit breakers, high-voltage circuit breakers, extra high-voltage circuit breakers, isolators/disconnectors, bus bars, and numerous other components utilised in power transmission and distribution.