Our Product / Services
Leading Manufacturer, Supplier & Retailer of Dry Powder Type BC Fire Extinguisher, Mechanical Foam Type Fire Extinguisher, Water CO2 Type Fire Extinguisher, Kitchen Fire Extinguisher and Carbon Dioxide Gas Type Fire Extinguisher.
Technical Specifications
| Capacity | 4 Kg. | 6 Kg. | 9 Kg. | 25 Kg. | 50 Kg. | 75 Kg. |
|---|---|---|---|---|---|---|
| Indian Standard | 15683 | 15683 | 15683 | 10568 | 10568 | 10568 |
| Type | Stored Pressure | Cartridge / CO2 Cylinder | ||||
| Extinguishing Media | dry Powder (BC Powder Confirming to IS 4308) | |||||
| Expellant | Nitrogen | CO2 Gas | ||||
| Operating Temperature | -10 to 550C | N/A | ||||
| Min. Effective Discharge | More Than 90% | More Than 85% | ||||
| Hydraulic Test Pressure | 27 Kg / cm2 | 30 Kg / cm2 | ||||
| Throw (Meters) | > 2 M | > 6 M | > 8 M | > 10 M | ||
| Discharge Time Secs Min. | 8 | 8 | 8 | 25-303 | 40-50 | 50-60 |
| Resistance to Impact | Yes | N/A | ||||
| Resistance to Vibrstion | Yes | N/A | ||||
| Tapping Test (500 Strokes) | Confirms | N/A | ||||
| Resistance to Corrosion (Salt Spray Test) | Yes | N/A | ||||
Technical Specifications
| Capacity | 4 Ltr. | 6 Ltr. | 9 Ltr. | 50 Ltr. |
|---|---|---|---|---|
| Indian Standard | 15683 | 15683 | 15683 | 13386 |
| Type | Stored Pressure | Cartridge Type | ||
| Extinguishing Media | Aqueous Film Forming (AFFF) Confirming to IS 4989 | |||
| Expellant | Nitrogen | CO2 | ||
| Operating Temperature | +5 to 550C | - | ||
| Min. Effective Discharge | 95% | 90% | ||
| Hydraulic Test Pressure | 27 Kg /cm 2 | 30 Kg /cm 2 | ||
| Throw Min. | 2 Meter | 10 Meter | ||
| Discharge Time (Sec.) | 13 | 40 | ||
| Resistance to Impact | Yes | N/A | ||
| Resistance to Vibration | Yes | N/A | ||
| Tapping Test (500 Strokes) | Confirms | N/A | ||
| Resistance to Corrosion | Yes | N/A | ||
| Fire Rating | 3A, 34B | N/A | ||
Technical Specifications
| Capacity | 6 Ltr. | 9 Ltr. | 50 Ltr. |
|---|---|---|---|
| Indian Standard | 15683 | 15683 | 13385 |
| Type | Stored Pressure | Stored Pressure | Cartridge Type |
| Extinguishing Media | Water | ||
| Expellant | Nitrogen | Nitrogen | CO2 |
| Operating Temperature | -5 to +550C | -5 to +550C | - |
| Min. Effective Discharge | More than 95% | ||
| Hydraulic Test Pressure | 27 kg / Cm2 | 27 kg / Cm2 | 30 kg / Cm2 |
| Throw Min. | 2 Meter | 2 Meter | 10 Meter |
| Discharge Time Min. (Sec.) | 13 | 13 | 180 |
| Resistance to Impact | Yes | Yes | N/A |
| Resistance to Vibration | Yes | Yes | N/A |
| Tapping Test (500 Strokes) | Confirms | Confirms | N/A |
| Resistance to Corrosion (Salt Spray Test) | Yes | Yes | N/A |
| Fire Rating | 3A | 3A | N/A |
Technical Specifications
| Capacity | 1 Ltr. | 2 Ltr. | 4 Ltr. | 6 Ltr. |
|---|---|---|---|---|
| Type | Stored Pressure | |||
| Extinguishing Media | Acetate Based Wet Chemical Solution | |||
| Expellant | Nitrogen | |||
| Operating Temperture | +5 to +550C | |||
| Min. Effective Discharge | More Than 95% | |||
| Hydraulic Test Pressure | 35 Kg / cm2 | |||
| Throw Min. | 1 Meter | 1 Meter | 2 Meter | 2 Meter |
| Discharge Time Min. | 8 Sec. | 8 Sec. | 13 Sec. | 13 Sec. |
| Resistance to Impact | Yes | |||
| Resistance to Vibration | Yes | |||
| Tapping Test (500 Strokes) | Confirms | |||
| Resistance to Corrosion | Yes | |||
Technical Specifications
| Capacity | 2 Kg. | 3 Kg. | 4.5 Kg. | 6.5 Kg. | 8 Kg. | 22.5 Kg. |
|---|---|---|---|---|---|---|
| Indian Standard | 15683 | 15683 | 15683 | 2878 | 2878 | 2878 |
| ISI Mark | Yes | - | Yes | Yes | - | - |
| Type | Stored Pressure | |||||
| Extinguishing Media | Carbon Dioxide Gas Confirming to IS 15222 | |||||
| Expellant | Self Expelling | |||||
| Filling Ration Max. | 0.667 | |||||
| Operating Tempersture | -10 to 550C | -30 to 550C | ||||
| Min. Effective Discharge | More Than 95% | |||||
| Throw Min. | 1 Meter | 1 Meter | 1 Meter | - | - | - |
| Discharge Time Secs. Min. | 8 | 8 | 8 | 10 | 15 | 20 |
| Resistance to Vibration | Yes | Yes | Yes | N/A | N/A | N/A |
| Fire Rating | 88 | 138 | 138 | N/A | N/A | N/A |
Technical Specifications
| Capacity | 1 Kg. | 2 Kg. | 4 Kg. | 6 Kg. | 9 Kg. |
|---|---|---|---|---|---|
| Indian Standard | 15683 | ||||
| Type | Stored Pressure | ||||
| Extinguishing Media | Dry Powder (ABC Powder Confirming to IS 14809) | ||||
| Expellant | Nitrogen | ||||
| Operating Temperature | -10 to +550C | ||||
| Min. Effective Discharge | More Than 90% | ||||
| Hydraulic Test Pressure | 27 kg /cm2 | ||||
| Throw More Than | 2 Meters | ||||
| Discharge Time (Sec.) | 8 | 8 | 8 | 13 | 13 |
| Resistance to Impact | Yes | ||||
| Resistance to Vibration | Yes | ||||
| Tapping Test (500 Strokes) | Confirms | ||||
| Resistance to Corrosion Salt Spray Test | Yes | ||||
| Fire Rating | 1A, BB | 1A, BB | 1A, BB | 2A, BB | 2A, BB |
Technical Specifications
| Capacity | 1 Kg. | 2 Kg. | 4 Kg. | 10 Kg. |
|---|---|---|---|---|
| Indian Standard | 15683 | |||
| Type | Stored Pressure | |||
| Extinguishing Media | HFC 227 as Based Clean Agent | |||
| Expellant | Nitrogen | |||
| Operating Temperature | -10 to +550C | |||
| Min. Effective Discharge | More than 95% | |||
| Hydraulic Test Pressure | 35 kg / Cm2 | |||
| Throw Min. | 1 Meter | 1 Meter | 1 Meter | 2 Meter |
| Discharge Time Min. | 8 Sec. | 8 Sec. | 8 Sec. | 13 Sec. |
| Resistance to Impact | Yes | |||
| Resistance to Vibration | Yes | |||
| Tapping Test (500 Strokes) | Confirms | |||
| Resistance to Corrosion | Yes | |||
| Fire Rating | BB | BB | 1A, 13 B | 3A |
Technical Specifications
| Capacity | 6 Kg. | 9 Kg. | 25 Kg |
|---|---|---|---|
| Type | Stored Pressure | ||
| Extinguishing Media | D Fire Powder Confirms to IS 4861 | ||
| Expellant | Nitrogen | ||
| Operating Temperature | -10 to 550C | ||
| Min. Effective Discharge | More than 85% | ||
| Hydraulic Test Pressure | 27 kg / cm2 | ||
| Throw Min. | 2 Meter | 2 Meter | 6 Meter |
| Discharge Time | 180 Sec. | 270 Sec. | 640 Sec. |
Technical Specifications
| Capacity | 2 Kg. | 5 Kg. | 10 Kg. | 15 Kg. | 25 Kg. |
|---|---|---|---|---|---|
| Type | Stored Pressure | ||||
| Extinguishing Media | Dry Powder (ABC/BC Powder Confirming to IS 14609 / IS 4308) or HFC 227 Based Clean Agent | ||||
| Expellant | Nitrogen | ||||
| Operating Temperature | 570C Onwards as per Requirements | ||||
| Operational Time (Secs.) | 5-7 | 8-10 | 10-15 | 18-24 | 30-38 |
| Coverage Area | 2-3m2 | 3-4m2 | 5-7m2 | 8-10m2 | 13-15m2 |
| Hydraulic Test Pressure | 27 Kg/cm2 | ||||