Our Product / Services
Our offered Product range includes Dry Powder Type BC Fire Extinguisher, Mechanical Foam Type Fire Extinguisher, Water CO2 Type Fire Extinguisher, Kitchen Fire Extinguisher and Carbon Dioxide Gas Type Fire Extinguisher.
Technical Specifications
| Capacity | 4 Kg. | 6 Kg. | 9 Kg. | 25 Kg. | 50 Kg. | 75 Kg. |
|---|---|---|---|---|---|---|
| Indian Standard | 15683 | 15683 | 15683 | 10568 | 10568 | 10568 |
| Type | Stored Pressure | Cartridge / CO2 Cylinder | ||||
| Extinguishing Media | dry Powder (BC Powder Confirming to IS 4308) | |||||
| Expellant | Nitrogen | CO2 Gas | ||||
| Operating Temperature | -10 to 550C | N/A | ||||
| Min. Effective Discharge | More Than 90% | More Than 85% | ||||
| Hydraulic Test Pressure | 27 Kg / cm2 | 30 Kg / cm2 | ||||
| Throw (Meters) | > 2 M | > 6 M | > 8 M | > 10 M | ||
| Discharge Time Secs Min. | 8 | 8 | 8 | 25-303 | 40-50 | 50-60 |
| Resistance to Impact | Yes | N/A | ||||
| Resistance to Vibrstion | Yes | N/A | ||||
| Tapping Test (500 Strokes) | Confirms | N/A | ||||
| Resistance to Corrosion (Salt Spray Test) | Yes | N/A | ||||
Technical Specifications
| Capacity | 4 Ltr. | 6 Ltr. | 9 Ltr. | 50 Ltr. |
|---|---|---|---|---|
| Indian Standard | 15683 | 15683 | 15683 | 13386 |
| Type | Stored Pressure | Cartridge Type | ||
| Extinguishing Media | Aqueous Film Forming (AFFF) Confirming to IS 4989 | |||
| Expellant | Nitrogen | CO2 | ||
| Operating Temperature | +5 to 550C | - | ||
| Min. Effective Discharge | 95% | 90% | ||
| Hydraulic Test Pressure | 27 Kg /cm 2 | 30 Kg /cm 2 | ||
| Throw Min. | 2 Meter | 10 Meter | ||
| Discharge Time (Sec.) | 13 | 40 | ||
| Resistance to Impact | Yes | N/A | ||
| Resistance to Vibration | Yes | N/A | ||
| Tapping Test (500 Strokes) | Confirms | N/A | ||
| Resistance to Corrosion | Yes | N/A | ||
| Fire Rating | 3A, 34B | N/A | ||
Technical Specifications
| Capacity | 6 Ltr. | 9 Ltr. | 50 Ltr. |
|---|---|---|---|
| Indian Standard | 15683 | 15683 | 13385 |
| Type | Stored Pressure | Stored Pressure | Cartridge Type |
| Extinguishing Media | Water | ||
| Expellant | Nitrogen | Nitrogen | CO2 |
| Operating Temperature | -5 to +550C | -5 to +550C | - |
| Min. Effective Discharge | More than 95% | ||
| Hydraulic Test Pressure | 27 kg / Cm2 | 27 kg / Cm2 | 30 kg / Cm2 |
| Throw Min. | 2 Meter | 2 Meter | 10 Meter |
| Discharge Time Min. (Sec.) | 13 | 13 | 180 |
| Resistance to Impact | Yes | Yes | N/A |
| Resistance to Vibration | Yes | Yes | N/A |
| Tapping Test (500 Strokes) | Confirms | Confirms | N/A |
| Resistance to Corrosion (Salt Spray Test) | Yes | Yes | N/A |
| Fire Rating | 3A | 3A | N/A |
Technical Specifications
| Capacity | 1 Ltr. | 2 Ltr. | 4 Ltr. | 6 Ltr. |
|---|---|---|---|---|
| Type | Stored Pressure | |||
| Extinguishing Media | Acetate Based Wet Chemical Solution | |||
| Expellant | Nitrogen | |||
| Operating Temperture | +5 to +550C | |||
| Min. Effective Discharge | More Than 95% | |||
| Hydraulic Test Pressure | 35 Kg / cm2 | |||
| Throw Min. | 1 Meter | 1 Meter | 2 Meter | 2 Meter |
| Discharge Time Min. | 8 Sec. | 8 Sec. | 13 Sec. | 13 Sec. |
| Resistance to Impact | Yes | |||
| Resistance to Vibration | Yes | |||
| Tapping Test (500 Strokes) | Confirms | |||
| Resistance to Corrosion | Yes | |||
Technical Specifications
| Capacity | 2 Kg. | 3 Kg. | 4.5 Kg. | 6.5 Kg. | 8 Kg. | 22.5 Kg. |
|---|---|---|---|---|---|---|
| Indian Standard | 15683 | 15683 | 15683 | 2878 | 2878 | 2878 |
| ISI Mark | Yes | - | Yes | Yes | - | - |
| Type | Stored Pressure | |||||
| Extinguishing Media | Carbon Dioxide Gas Confirming to IS 15222 | |||||
| Expellant | Self Expelling | |||||
| Filling Ration Max. | 0.667 | |||||
| Operating Tempersture | -10 to 550C | -30 to 550C | ||||
| Min. Effective Discharge | More Than 95% | |||||
| Throw Min. | 1 Meter | 1 Meter | 1 Meter | - | - | - |
| Discharge Time Secs. Min. | 8 | 8 | 8 | 10 | 15 | 20 |
| Resistance to Vibration | Yes | Yes | Yes | N/A | N/A | N/A |
| Fire Rating | 88 | 138 | 138 | N/A | N/A | N/A |
Technical Specifications
| Capacity | 1 Kg. | 2 Kg. | 4 Kg. | 6 Kg. | 9 Kg. |
|---|---|---|---|---|---|
| Indian Standard | 15683 | ||||
| Type | Stored Pressure | ||||
| Extinguishing Media | Dry Powder (ABC Powder Confirming to IS 14809) | ||||
| Expellant | Nitrogen | ||||
| Operating Temperature | -10 to +550C | ||||
| Min. Effective Discharge | More Than 90% | ||||
| Hydraulic Test Pressure | 27 kg /cm2 | ||||
| Throw More Than | 2 Meters | ||||
| Discharge Time (Sec.) | 8 | 8 | 8 | 13 | 13 |
| Resistance to Impact | Yes | ||||
| Resistance to Vibration | Yes | ||||
| Tapping Test (500 Strokes) | Confirms | ||||
| Resistance to Corrosion Salt Spray Test | Yes | ||||
| Fire Rating | 1A, BB | 1A, BB | 1A, BB | 2A, BB | 2A, BB |
Technical Specifications
| Capacity | 1 Kg. | 2 Kg. | 4 Kg. | 10 Kg. |
|---|---|---|---|---|
| Indian Standard | 15683 | |||
| Type | Stored Pressure | |||
| Extinguishing Media | HFC 227 as Based Clean Agent | |||
| Expellant | Nitrogen | |||
| Operating Temperature | -10 to +550C | |||
| Min. Effective Discharge | More than 95% | |||
| Hydraulic Test Pressure | 35 kg / Cm2 | |||
| Throw Min. | 1 Meter | 1 Meter | 1 Meter | 2 Meter |
| Discharge Time Min. | 8 Sec. | 8 Sec. | 8 Sec. | 13 Sec. |
| Resistance to Impact | Yes | |||
| Resistance to Vibration | Yes | |||
| Tapping Test (500 Strokes) | Confirms | |||
| Resistance to Corrosion | Yes | |||
| Fire Rating | BB | BB | 1A, 13 B | 3A |
Technical Specifications
| Capacity | 6 Kg. | 9 Kg. | 25 Kg |
|---|---|---|---|
| Type | Stored Pressure | ||
| Extinguishing Media | D Fire Powder Confirms to IS 4861 | ||
| Expellant | Nitrogen | ||
| Operating Temperature | -10 to 550C | ||
| Min. Effective Discharge | More than 85% | ||
| Hydraulic Test Pressure | 27 kg / cm2 | ||
| Throw Min. | 2 Meter | 2 Meter | 6 Meter |
| Discharge Time | 180 Sec. | 270 Sec. | 640 Sec. |
Technical Specifications
| Capacity | 2 Kg. | 5 Kg. | 10 Kg. | 15 Kg. | 25 Kg. |
|---|---|---|---|---|---|
| Type | Stored Pressure | ||||
| Extinguishing Media | Dry Powder (ABC/BC Powder Confirming to IS 14609 / IS 4308) or HFC 227 Based Clean Agent | ||||
| Expellant | Nitrogen | ||||
| Operating Temperature | 570C Onwards as per Requirements | ||||
| Operational Time (Secs.) | 5-7 | 8-10 | 10-15 | 18-24 | 30-38 |
| Coverage Area | 2-3m2 | 3-4m2 | 5-7m2 | 8-10m2 | 13-15m2 |
| Hydraulic Test Pressure | 27 Kg/cm2 | ||||