The company stands tall among the successful Manufacturers, Suppliers and Exporters of OLTC Transformers. Our range of OLTC Transformers is used in paper mills, sugar mills, rolling mills, steel mills etc. Bulk orders of the Transformers are processed by us as per the specific requirements of the buyers. One can obtain it at nominal rates.
Range : 6.3KVA to 4000KVA
About Oltc Transformers :
On load tap Changer (OLTC) is used with higher capacity transformers where HT side voltage variation is frequent and a nearly constant LT voltage is required. OLTC is coupled with the transformer itself. Multiple tapings from HV windings are brought to the OLTC chamber and connected to fixed contacts. Moving contacts rotates with the help of rotating mechanism usually a Geneva mechanism having a spindle. The spindle can be rotated manually as well as electrically with a motor. Motor is connected in such a way that it can rotate in both the directions suhc as to rotate the OLTC moving contancts clockwise and anti clockwise. Two push buttons are fitted on the LCP (low control panel) to rotate the motor and hence the OLTC contacts. This movement of contacts thus controls the output LV voltage of the transformer. So rotating of the OLTC contacts with spindle or push button in this way is manual process. In case this process of rotating the OLTC contacts and hence controlling the LV side voltage is to be done automatically then a RTCC (remote tap changer controller) is installed with the transformer ht panel. The RTCC panel which has sensors which sense the output voltage and accordingly sends signal to LCP and LCP in turns rotates the motor as per signal received from the RTCC.
Applications :
Chemical Plant, Botting Plant.
Paper mills, Sugar mills, Rolling mills, Steel mills etc.
Industries which rely heavily on automation, where electronic cards, PLC and VFDs are used in operations and acutation.
Hospitals, Schools, Insitution etc.
Specifications
Item |
Description |
---|---|
Range of Transformer |
250 KVA - 5000 KVA (6.6 Kv, 11 KV, 22 KV, 33KV) |
Vector Group |
Unless or otherwise specified, the transformers will be connected as per Vector Group reference DYn 11 in accordance with international Practice. |
Core |
The core used is best qualtiy cold rolled grain oriented and laser processed silicon steel sheet. They provide low iron loss, low noise, and compact size and have the best performance for high efficiency transformers. |
Windings |
We use high quality conductor of copper in our products. Round or rectangular copper wires / Strips ribbed with thermally upgraded insulting paper are applied in oil immersed transformers. The winding have a compact size, excellent heat transmission, Low load loss, high lighting impulse resistivity and outstanding anti-short-circuit strength. |
Insulation |
Our oil-immersed transformers are insulated by electrical grade insulated press board and thermally upgrade insulating Kraft Paper. |
Tappings |
Tapings + 5% to - 15% in steps of 1.25% or as per customer's requirement. |
Oil |
Dehydrated EHV-Grade transformers oil as per IS 355 (1993) with latest amendments is used for proper insulation and cooling after testing for all the parameters viz a viz resistivity, tan delta, BDV, neutralization, flash point etc. |
Bushings |
For HV/LV bushings : Good quality porcelain bushings are used on the high voltage terminals / low Voltage terminals. Optional bushing wells, inserts and elbows are available upon request. High voltage cables are inserted directly and show no live parts Outside. |
Accessories |
The accessories include an oil filling hole, oil drain valve, safety valve, standard thermometer, oil level gauge, skid wheel, jacking pad, breather, earthing terminal |
Optional Accessories |
Buchholz realy, cooling fan, HV & LV cable box, cable duct, bus bar duct, dial-type thermometer, oil level gauge, OTI (Oil Temp Indicator), WTI (Winding temp. Indicator), Marshling box, pressure release valve, protective fuse and lightening arresters are available upon customer's request extra cost. |
We are a major Manufacturer and Supplier of a range of cutting-edge Distribution Transformers. Manufactured in compliance with IS 2026/1977, IS 1180/1989 or as per the requirements of the customers, our Distribution Transformers are designed to function effectively for a long time, without needing any maintenance. Testing of the Distribution Transformers is carried out according to IS 2026 and the following tests are done: Dynamic short circuit, impulse voltage tests and temperature rise test etc.
Availability
Array Offered
Components
Salient Features
Accessories Available
Optional Accessories (available at extra cost)
Installation
Demanded for
Isolation /Ultra Isolation Transformer is manufactured by us as per IS: 2026 specifications and is made available in standard as well as customized models to serve the specific needs of the customers. Several shielding techniques in our Isolation /Ultra Isolation Transformer effectively reduce interwinding capacitance to less than 0.005 Pico farad and causes an increase in D.C. Isolation up to 1000 Mega ohms.
Range : 6.3KVA to 4000KVA
Types of Low impedance paths for passing noises to secondary and vice-versa
Why Our Isolation /Ultra Isolation Transformer?
Effective for
Specially Designed For
We offer a wide range of Induction Furnace Transformer, which is manufactured in accordance with IS: 2026 specifications. Manufactured using superior quality components and latest techniques, the Induction Induction Furnace Transformer features electrostatic shielding between the primary and secondary winding to avoid problems of earth fault tripping. Required for arc furnaces and induction furnaces, the performance of the Induction Induction Furnace Transformer has made us a reputable Manufacturer and Supplier in the industry.
Range : - 6.3KVA to 4000KVA
Capacity
Key features
Demanded by
We are bracketed among the trusted Manufacturers, Suppliers and Exporters of Type Test Transformers. The Transformers we make available are highly efficient and are highly energy saver. Our Transformers undergo various quality-tests before the final dispatch of the Transformers. Bulk orders of the Transformers are processed by us as per the specific requirements of the buyers.
Type Test Transformers :
These are our range of distribution transformers which are type tested from ERDA. We have various approved ratings of our different transformers. Such as we have 3 and 4 Star rating respectively approved for our 16, 25, 100, 200 KVAtransformers.l
The transformers besides routine testing undergoes type test in which following test are done :
Lightening Impulse Test
Short Circuit Test
Temperature Rise Test
Air Pressure Test
Vacuum Test
Magnetic Balance Test
Permissible Flux Density and Overfluxing test
These Transformers are highly efficient and are highly energy saver. They have fairly low losses. GTB is approved supplier of various state electricity boards such as PSPCL, HPSEB etc. We participate in tenders of star rated transformers and also participate for repair tenders of state Electricity boards
Specifications
Technical Specifications |
16(4*) |
25(3*) |
63(4*) |
100 (3*) |
200 (4*) |
---|---|---|---|---|---|
Rated Input |
11000 v |
11000v |
11000v |
11000v |
11000v |
Rated Output |
433v |
433v |
433v |
433v |
433v |
Frequency |
50 Hz +/-3Hz |
50 Hz +/-3Hz |
50 Hz +/-3 Hz |
50 Hz +/-3Hz |
50 Hz+/-3Hz |
Input Configuration |
Delta |
Delta |
Delta |
Delta |
Delta |
Output Configuration |
Star |
Star |
Star |
Star |
Star |
Vector Group |
Dyn11 |
Dyn11 |
Dyn11 |
Dyn11 |
Dyn11 |
Current LV (amp) |
21.33 |
33.33 |
84.00 |
133.34 |
266.68 |
Current HV (lamp) |
0.84 |
1.31 |
3.31 |
5.25 |
10.5 |
Losses at 50% load (w) |
135 |
210 |
340 |
520 |
780 |
Losses at 100% Load (w) |
440 |
695 |
1140 |
1800 |
2115 |
% impedance at 75 oC |
4.5 |
4.5 |
4.5 |
4.5 |
4.5 |
Core |
Prime Imported Crgo |
Prime Imported Crgo |
Prime Imported Crgo |
Prime Imported Crgo |
Prime Imported Crgo |
Winding |
EG Aluminum Super ename/dpc |
Eg Aluminum super Enamel/Dpc |
Eg Aluminum Super enamel/Dpc |
EG Aluminium Super enamel/dpc |
Eg Aluminium Super ename/Dpc |
Cooling |
Onan |
Onan |
Onan |
Onan |
Onan |
Max. Ambient Temperature |
50 oC |
50 oC |
50 oC |
50 oC |
50 oC |
Max. oil temperature rise |
35oC |
35 oC |
35 oC |
35 oC |
35 oC |
Max. Winding Temperature rise |
40 oC |
40 oC |
40 oC |
40 oC |
40 oC |
HV side High voltage Withstand test |
28kv |
28kv |
28kv |
28kv |
28kv |
LV side high voltage withstand test |
3 Kv |
3 Kv |
3 Kv |
3kv |
3 Kv |