Our Products
We offer a complete product range of LT Cables & Wires
We put at the client’s disposal, the LT Cables & Wires that conforms to the established industry standards. We are referred as the remarkable Manufacturer and Supplier of the LT Cables & Wires from Agra, India. Available in the variety of specifications, these LT Cables & Wires are lightweight, have better resistance and high current carrying capacity. We offer the quality-assured Cables in tamper-proof packaging, at the rational prices.
Specifications
| Nom. Cross Sectional Area Sq.mmdff |
Nom. Thickness of PVC insulation mm |
Unamoured | Armoured | Max. DC Conductor Resistance at 20oC 0hm/km |
A.C. Current Rating | ||
| Approx. Overall Dia. | Nom. Steel Armour Size mm |
Nom. Thickness of PVC insulation mm |
In Air Amps |
In Ground Amps |
|||
| 25 | 1.2 | 24 | 4x0.8 | 70 | 1.2 | 70 | 76 |
| 35 | 1.2 | 26 | 4x0.8 | 86 | 0.87 | 86 | 92 |
| 50 | 1.4 | 29 | 4x0.8 | 105 | 0.64 | 105 | 110 |
| 70 | 1.4 | 34 | 4x0.8 | 130 | 0.44 | 130 | 135 |
| 95 | 1.6 | 37 | 4x0.8 | 155 | 0.32 | 155 | 165 |
| 120 | 1.6 | 41 | 4x0.8 | 180 | 0.25 | 180 | 185 |
| 150 | 1.8 | 46 | 4x0.8 | 205 | 0.21 | 205 | 210 |
| 185 | 2 | 49 | 4x0.8 | 240 | 0.16 | 240 | 235 |
| 240 | 2.2 | 56 | 4x0.8 | 280 | 0.13 | 280 | 275 |
| Nom. Cross Sectional Area Sq.mm |
Nom. Thickness of PVC insulation mm |
Unamoured | Armoured | Max. DC Conductor Resistance at 20ºC 0hm/km |
A.C. Current Rating | ||
| Approx. Overall Dia. | Nom. Steel Armour Size mm | Nom. Thickness of PVC insulation mm | In Air Amps |
In Ground Amps |
|||
| 2.5 | 0.9 | 13.8 | 1.4 | 15.5 | 12.1 | 21 | 25 |
| 4 | 1 | 15.5 | 1.4 | 15.8 | 7.41 | 27 | 32 |
| 6 | 1 | 16.5 | 1.4 | 17 | 3.08 | 35 | 40 |
| 10 | 1 | 18.4 | 1.4 | 19.2 | 4.61 | 47 | 55 |
| 16 | 1 | 20.5 | 4x0.8 | 21.2 | 1.91 | 59 | 70 |
| 25 | 1.2 | 22 | 4x0.8 | 21.2 | 1.2 | 78 | 90 |
| 35 | 1.2 | 23.5 | 4x0.8 | 22.5 | 0.87 | 99 | 110 |
| 50 | 1.4 | 26 | 4x0.8 | 25 | 0.64 | 125 | 135 |
| 70 | 1.4 | 30.4 | 4x0.8 | 28.5 | 0.44 | 150 | 160 |
| 95 | 1.6 | 33.5 | 4x0.8 | 31 | 0.32 | 185 | 190 |
| 120 | 1.6 | 37 | 4x0.8 | 33.5 | 0.25 | 210 | 210 |
| 150 | 1.8 | 37 | 4x0.8 | 37.5 | 0.21 | 240 | 240 |
| 185 | 2 | 40.5 | 4x0.8 | 40.5 | 0.16 | 275 | 275 |
| 240 | 2.2 | 45 | 4x0.8 | 45 | 0.13 | 325 | 320 |
| Normal Area of Conductor | Numbers/Nom. Dia of Wire | Thickness of Insulation | Approx Overall Diameter | Current carrying capacity # | Resistance (max.) per Km @ 20ºC | |
| In Coduit | In Surface | |||||
| Sq. mm | mm | mm | mm | Amps | Amps | Ohms |
| 0.75 | 24/.2 11/.3 | 0.6 | 2.3 | 6 | 7 | 26 |
| 1.0 | 32/.2 14/.3 | 0.7 | 2.8 | 11 | 12 | 18.10 |
| 1.5 | 48/.2 22/.3 | 0.7 | 3.1 | 13 | 16 | 12.10 |
| 2.5 | 36/.3 | 0.8 | 3.8 | 18 | 22 | 7.41 |
| 4.0 | 56/.3 | 0.8 | 4.4 | 24 | 29 | 4.95 |
| 6.0 | 84/.3 | 0.8 | 5.0 | 31 | 37 | 3.30 |
Image