Our Products
Our offered Product range includes Humidity and Temperature Transmitter and Pressure Transmitter.
Features :
Typical Areas of Application
TRH-30x Series uses a thin film polymer capacitor to sense Relative Humidity & a thin film RTD to accurately sense Temperature. The Output signal given is 4 - 20 mA analog output requiring a current loop supply of 12 - 30 VDC. The electronics is housed in awatertight IP-65 enclosure.
Technical Specifications
| Measuring Range | 5 to 95% RH |
| 0 to 70°C | |
| 0 Accuracy @ 25oC | ± 2% RH , ± 0.3° C |
| Sensors | Humidity : Thin-film Capacitor |
| Temperature : Pt100 | |
| Electronics Operating temp | 0 to 50°C |
| Response | <15 sec |
| Long-term Stability | Better than 1% RH per year |
| Output | 4-20mA (0~100%RH; 0~100ºC) other outputs on request |
| Load Resistance | Maximum 300 Ohms |
| Supply Voltage | 12 to 30 VDC |
| Housing | ABS plastic watertight enclosure |
| Protection | IP-65 |
| Weight | Approx 180gms |
Ordering Information
| Model | Descriptions | |
|---|---|---|
| TRH - 304 | Humidity / Temperature Transmitter | |
| TRH - 305 | Humidity Transmitter | |
| SHAPE (Mounting) | W | Wall Mount Type |
| D | Duct Mount Type | |
| S | Separated Type | |
On-Site Calibration & Wiring
Wall Mount Type
Duct Mount Type
Mounting
The stainless steel pressure port makes the sensors resistant to aggressive media such as Oil, Fuel, Diesel, Waste Water and other aggressive liquids. The sensors are Factory calibrated using the state-of-the-art, highly productive electronic trimming technology.
Features :
Mechanical Properties Ceramic :
| Wetted Parts | Ceramic |
|---|---|
| Body | Stainless steel |
| Fixing Spanner | 27 mm |
| Mounting Orientation | Any Directions |
Operating Conditions :
| Operating Temperature Range | -40..125oc |
|---|---|
| Storage Temperature Range | -20...50oc |
| Humidity | 95% RH |
Table A
| Order Code | Operating Range | |
|---|---|---|
| EQ-PT 1000-1 | 0 to 2 bar | Low Range |
| EQ-PT 1000-2 | 0 to 6 bar | |
| EQ-PT 1000-3 | 0 to 10 bar | |
| EQ-PT 1000-4 | 0 to 16 bar | |
| EQ-PT 1000-5 | 0 to 25 bar | |
| EQ-PT 1000-6 | 0 to 40 bar | |
| EQ-PT 1000-7 | 0 to 100 bar | |
| EQ-PT 1000-8 | 0 to 250 bar | |
| EQ-PT 1000-9 | 0 to 400 bar | High range |
| EQ-PT 1000-A | 0 to 600 bar | |
| EQ-PT 1000-X | -1 to 10 bar | Absolute Pr |
Dimensions And Application Circuit
Wiring Diagram For Pressure Transmitter