Features of Products :
- The panel consists of 2 to 60 Zones.
- The panel complies with IS 2189 specification.
- The panel has separate fire and fault indications.
- The panel also has separate fire and common fault relay.
- The panel comprises of a 4Amp power supply unit.
- Battery backup is provided along with the AC supply.
- The panel is equipped with a 24VdC piezoelectric buzzer for fault and fire.
Technical Specification :
INTERNAL POWER SUPPLY UNIT
- Constant potential battery charger 27.5V DC Adjustable.
- Output Current limited to 2 A.
- Low battery voltage monitored at 18 V DC Adjustable.
- Battery charger monitoring for failure.
- Mains supply monitoring for failure.
- Mains supply input voltage range 230V AC + or – 10 %, 50 Hz.
- Total panel quiescent current 50mA nominal.
- Approx. Standby time 4.5 AH 36 hrs.
- Battery recharge time from discharge 1 Hr. approx.
INTERNAL RELAY CONTACT RATING
- Fire Relay 5 Amps S.P. 240 V DC.
- Common fault relay 5 Amps S.P. 240 V DC.
- Aux. Fire relay 5 Amps S.P. 240 V AC.
Panel Indications :
- System ON Green LED - System normal.
- Common Fault Amber LED – Internal buzzer will sound intermittently.
- Common Fire Red LED - Detector activated.
- Zone fault Amber LED – Indicates zone wiring and detector faults.
- Zone fire Red LED – indicates zone where fire has been detected.
- AC fail Amber LED – Indicates loss of mains.
- DC fail Amber LED – Indicates battery fault.
- Batt. Low Amber LED – Indicates battery supply below 18V DC.
External Controls :
- Sound : To sound external as well as internal sounders.
- Silence : To silence external as well as internal sounders.
- Reset : Lamp test & resets the panels.
- Isolate : The zone to add/clean detectors.
- Test : International standard walk test.
- Auto/manual : Amplifier in auto/manual mode.
- Volume : Increase/ decrease amplifier volume.
- Call All : Announcement to all zones simultaneously.
- Selected switch for individual zone announcement.