We are leaders in the market for providing best range of Water Pre-Heaters

Water Pre-Heaters

Typically, the flue gases leaving a modern 3-pass shell boiler are at temperatures of 200 to 300 C. Thus, there is a potential to recover heat from these gases. The flue gas exit temperature from a boiler is usually maintained at a minimum of 175 C, so that the sulphur oxides in the flue gas do not condense and cause corrosion in heat transfer surfaces. When a clean fuel such as natural gas, LPG or gas oil is used, the economy of heat recovery must be worked out, as the flue gas temperature may be well below 200C.

The potential for energy saving depends on the type of boiler installed and the fuel used. For a typically older model shell boiler, with a flue gas exit temperature of 260C, an economizer could be used to reduce it to 200C, increasing the feed water temperature by 15C. Increase in overall thermal efficiency would be in the order of 3%. For a modern 3-pass shell boiler firing natural gas with a flue gas exit temperature of 140C a condensing economizer would reduce the exit temperature to 65C increasing thermal efficiency by 5%.

Depending on fuel used for firing, THERMIN ENERGY provides bare tube, finned tube, gilled tube Economisers /Water Preheaters.