Our Products
Our Complete range of products are House Service Cutout, under Ground Single Pole Cutouts, SINGLE POLE CUTOUTS, Cast Aluminium Cutouts and DMC Heavy Duty Cutouts.
| Type/Data | 60/80A SP | 100A SP | 60/80A SPN | 100A SPN | 100A TPN | |||||
| Rated Operating Voltage Ue | 415V | 415V | 415V | 415V | 415V | |||||
| Rated Operational Current in | 60/80A | 100A | 60/80A | 100A | 100A | |||||
| Rated Insulation Voltage Ui | 660V | 660V | 660V | 660V | 660V | |||||
| Rated Short Time Current Lcw | 12 kA Peak 0.02 Sec | 18 kA Peak 0.02 Sec | 12 kA Peak 0.02 Sec | 18 kA Peak 0.02 Sec | 18 kA Peak 0.02 Sec | |||||
| Impulse Voltage U imp | 6 kV with 1.2/50µs waveform | 6 kV with 1.2/50µs waveform | 6 kV with 1.2/50µs waveform | 6 kV with 1.2/50µs waveform | 6 kV with 1.2/50µs 6 kV with 1.2/50µs waveform | |||||
| Cable Size upto | 35 sq. mm | 35 sq. mm | 35 sq. mm | 35 sq. mm | 35 sq. mm | |||||
| Fuse Link Cartridge | As Per BS 1361 Type II a* | As Per BS 1361 Type II b | As Per BS 1361 Type II a* | As Per BS 1361 Type II b | As Per BS 1361 Type II b | |||||
| Sealing Arrangement Provided | Yes | Yes | Yes | Yes | Yes |
| Technical Details | 100A | 160A | 250A | |||||||
| Housing Material | Cast Aluminium | Cast Aluminium | Cast Aluminium | |||||||
| Rated Operation Current | 100 A | 160 A | 250 A | |||||||
| Rated Insulation Voltage | 415 v | 415 v | 415 v | |||||||
| Fuse Carrier | Finger Grip Type | Finger Grip Type | Finger Grip Type | |||||||
| Power Frequency Withstand | 3.75kV for 1min. | 3.75kV for 1min. | 3.75kV for 1min. | |||||||
| Cable Type | Suitable for Use With 4Core XLPE Insulated Cable of Size 70mm2 | Suitable for Use With 4Core XLPE Insulated Cable of Size 120mm2 | Suitable for Use With 4Core XLPE Insulated Cable of Size 240mm2 | |||||||
| Fuse Link | 82.5 mm J Type | 82.5 mm J Type | 82.5 mm J Type | |||||||
| Sealing Arrangement Provided | yes | yes | yes | |||||||
| Types Available | Indoor and Outdoor | Indoor and Outdoor | Indoor and Outdoor |
| TECHNICAL DETAIL | 400A | 630A | ||||||||
| CATALOGUE NUMBER | LVHDC400I | LVHDC630I | ||||||||
| HOUSING MATERIAL | DMC | DMC | ||||||||
| RATED OPERATION CURRENT | 400A | 630A | ||||||||
| RATED OPERATIONAL VOLTAGE | 415V | 415V | ||||||||
| RATED INSULATION VOLTAGE | 500 V | 500 V | ||||||||
| FUSE CARRIER | FINGER GRIP TYPE | THROUGH GRIP TYPE | ||||||||
| POWER FREQUENCY WITHSTAND | 3.75 kV FOR 1 MIN. | 3.75 kV FOR 1 MIN. | ||||||||
| CABLE TYPE | SUITABLE FOR USE WITH 240 SQMM CABLE | SUITABLE FOR USE WITH 300 SQMM CABLE | ||||||||
| FUSE LINK | 82.5 mm J type | 92 mm J type | ||||||||
| SEALING ARRANGEMENT PROVIDED | YES | YES | ||||||||
| TYPES AVAILABLE | INDOOR | INDOOR | ||||||||
| IP PROTECTION WITH COVER AND CARRIER IN PLACE | IP 3X | IP 3X |
| TECHNICAL DETAIL | TYPE-A1 | TYPE-B1 | ||||||||
| HOUSING MATERIAL | DMC | DMC | ||||||||
| RATED OPERATION CURRENT | 25 A | 25 A | ||||||||
| RATED OPERATIONAL VOLTAGE | 250V | 250V | ||||||||
| RATED INSULATION VOLTAGE | 500V | 500V | ||||||||
| RATED SHORT TIME CURRENT | 6 KA PEAK | 6 KA PEAK | ||||||||
| IMPULSE VOLTAGE | 6 KV | 6 KV | ||||||||
| CABLE TYPE | TWO CORE CABLE FOR I/C & O/G | FOUR CORE CABLE FOR I/C & O/G | ||||||||
| FUSE LINK | 2-25 A TAG TYPE AS PER BS 7654 | 2-25 A TAG TYPE AS PER BS 7654 | ||||||||
| SEALING ARRANGEMENT PROVIDED | YES | YES |