| Features : |
| |
| Technical Specification |
|
MGS Standard |
| |
| Power Supply |
|
12/24V AC/DC ± 20%(IR 24V AC/DC) |
| |
| Power Consumption |
|
EC (24V): 45.7mA SC: 91mA |
| |
| Power Monitoring* |
|
Green LED |
| |
| Visual Alarm* |
|
Red LED |
| |
| Audible Alarm* |
|
Sounder, enabled/disabled |
| |
| Fault monitoring |
|
Red LED ON – Green OFF |
| |
| Fault state |
|
0-1V, 0-2mA |
| |
| Analogue Outputs |
|
0-5V, 1-5V, 0-10V, 2-10V, 4-20mA |
| |
| Digital Outputs* |
|
1 Relay rated 1 Amp/24 V d.c /120 V a.c
Selectable delay: 0,1,5,10min |
| |
| IP Rating |
|
IP41 OR IP66 |
| |
| Dimensions and Weight |
|
86 x 142 x 53 mm 180 g |
| |
| Standard Compliance |
|
WEEE RoHS CE, EXD |
| |
|
| |
| Sensor Information |
|
ElectrochemicalEC |
|
Semiconductor withfilter (multigas) SC |
|
InfraredIR |
| |
| Typical MeasurementRang |
|
0-1,000 ppm |
|
10-1,000 ppm |
|
ppm - % |
| |
| Temprature Rang |
|
A: -20°C to +40°C
B: -40°C to +40°C
|
|
-40°C to +50°C |
|
-40°C to +50°C |
| |
|
Humidity Range
non condensing
|
|
0 to 95% |
|
0 to 95% |
|
0 to 95% |
| |
| Typical Sensor Life |
|
3 yrs |
|
5-8 yrs |
|
8-10yrs |
| |
| Alarm threshold T50 |
|
19 sec |
|
76 sec(filtered) |
|
25 sec |
| |
| T90 |
|
47 sec |
|
215sec(filtered) |
|
90sec |
| |
| Recovery Time |
|
900 sec |
|
600 sec |
|
210 sec |
| |
| Linearity |
|
|
|
Linear over calibrated range |
|
|
| |
| Calibration |
|
Local regulations may specify the procedure and frequency requiredStandards |
| |
| Requirements |
|
generally require at least annual testing or calibration. Refer to Murco for
instructions. Semiconductor sensors are non-selective, but calibrated to a specific |
|
| |
|
|
|
|