Listing ID #549064
Company Information
Ask for more detail from the seller
Contact SupplierThe XLPE OR PVC insulated and PVC sheathed 3-core flat Submersible Cables are used for electrically connecting the submersible pump motors. These pumps are widely applicable for irrigation, mine dewatering, drinking water supply, swimming pools, fountains, offshore drilling rigs and many more. Holding expertise as a Submersible Cables Manufacturer, we offer them in different variants. They are manufactured from bright-annealed 99.97% pure bare copper conductors and have low conductor resistance. The inner cores of these cables are insulated with a special grade XLPE or PVC compound. The robust outer HR PVC jacket protects the cables from oils, greases, various chemicals and abrasions, thereby giving long functional life and electrical safety. Counting on afore mentioned attributes, we are a major Submersible Pump Cables Supplier in India.
Features
Conductor | Insulation | Shesth | Overall Dimension | Conductor Resistance @ 20oC (max.) ohms/km. |
Current Carrying Capacity @ 40oC Amps |
||
Area sq. mm |
No. of Strands / Dia. mm | Thickness (Nom)mm |
Thickness (Nom)mm |
Width (Approx.) 'W' mm |
Height(Approx.) 'H' mm |
||
1.5 | 22/0.30+ | 0.6 | 0.9 | 10.3 | 4.9 | 12.1 | 14 |
2.5 | 36/0.30+ | 0.7 | 1 | 12.3 | 5.8 | 7.41 | 18 |
4 | 56/0.30++ | 0.8 | 1 | 14.8 | 6.6 | 4.95 | 26 |
Conductor | Insulation | Shesth | Overall Dimension | Conductor Resistance @ 20oC (max.) ohms/km. | Current Carrying Capacity @ 40oC Amps | ||
Area sq. mm | No. of Strands / Dia. mm | Thickness (Nom)mm | Thickness (Nom)mm | Width (Approx.) 'W' mm | Height(Approx.) 'H' mm | ||
6 | 84/0.30 | 1 | 1.15 | 18.7 | 7.9 | 3.3 | 31 |
10 | 140/0.30 | 1 | 1.4 | 23.7 | 9.9 | 1.91 | 42 |
16 | 226/0.30 | 1 | 1.4 | 28 | 11.4 | 1.21 | 57 |
25 | 354/0.30 | 1.2 | 2 | 35.5 | 14.7 | 0.78 | 72 |
35 | 495/0.30 | 1.2 | 2 | 39.5 | 16.2 | 0.55 | 90 |
50 | 703/0.30 | 1.4 | 2.2 | 45.5 | 18.3 | 0.39 | 115 |
70 | 360/0.50 | 1.4 | 2.2 | 51 | 20 | 0.27 | 143 |
95 | 475/0.50 | 1.6 | 2.4 | 60 | 23.5 | 0.21 | 165 |
Note : The number of wires and strand diameter will be such as to satisfy the requirements of conductor resistance as per IS 8130 : 1984
HP Vs Current : The full load current for submersible pumps motors, 3 phase, 50 cycles, 415 - 425 V.
HP | 5 | 7.5 | 10 | 12.5 | 15.5 | 17.5 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Amp | 7.5 | 11 | 14.9 | 18.9 | 22.5 | 25.5 | 28.4 | 35.6 | 50.4 | 50.4 | 58.1 | 62.1 | 67.5 | 73.8 | 81 | 87.3 | 93.6 | 100.8 | 108 |
Multiply the current capacity of the cable by factors given below for various ambient temperatures.
Ambient Temperature oC | 30 | 35 | 40 | 45 | 50 |
---|---|---|---|---|---|
Rating Factor | 1.09 | 1.04 | 1 | 0.95 | 0.77 |