Contact SupplierDrawing No. | GC-PN-01 | GC-PN-02 | ||
Highest system voltage | Kv | 24 | 24 | |
Working voltage | Kv | 22 | 22 | |
Total Creepage Distance (Nominal) | Mm | 432 | 560 | |
Protected Creepage Distance (Nominal) | Mm | 210 | 290 | |
Visible Discharge Voltage | Kv | 18 | 18 | |
Mechanical Failing load | Kn | 10 | 10 | |
Power Frequency withstand Voltage | Wet | Kv | 55 | 75 |
Dry | Kv | 65 | 85 | |
Power Frequency Flashover Voltage | Wet | Kv | 65 | 85 |
Dry | Kv | 75 | 95 | |
Impulse withstand voltage | Positive | Kvp | 140 | 150 |
Negative | Kvp | 150 | 160 | |
Puncture Voltage | Kv | 140 | 150 | |
Thimble-IS : 2486(Part II)/BS : 3288 (Part II) | Large | Large | ||
Net weight (approx) | kg. | 4.5 | 7.0 | |
Specification as per IS : 731, BS : EN 60383, IEC : 383 | ||||