Company Information
Ask for more detail from the seller
Contact SupplierThe cr7 723t card provides 14 differential or 28 single-ended inputs. The cr7 723t also contains an rtd that provides a reference junction for thermocouple measurements that is accurate to ±0.1°c over the range of -40° to +60°c.
each cr7 723t is placed in an open slot on the cr7 720 or cr7 720xl io module (the cr7 720 can accommodate up to 7 cards; the cr7 720xl can hold up to 14). More than one cr7 723t card can be used in one io module.
features
provides 14 differential or 28 single-ended inputs
measures analog voltages in the range of ±5 v
includes an rtd that provides a reference for thermocouple measurements
specifications
analog channels: 28 single-ended (14 differential)
analog accuracy: ±0.01% fsr, 0° to 40°c
input voltage range: ±5 vdc
analog resolution: to 50 nv
rtd accuracy: ±0.1°c (-40° to +60°c)