    Infinity and Entity from Trinity are digital energy meters for use in three phase electrical systems for sub-metering applications. The design of these meters is based on proven microcontroller....
    View More Details
    Send Enquiry

    Company Information

    • calendar Member Since 15 Years
    • building Nature of Business Manufacturer

    Ask for more detail from the seller

    Contact Supplier
    Report incorrect details
    • Product Details

    • Company Details

    no_img_icon

    Infinity and Entity from Trinity are digital energy meters for use in three phase electrical systems for sub-metering applications.

    The design of these meters is based on proven microcontroller technology; with front end ASICs resulting in compact and accurate energy metering. The accuracy of the meters is maintained even under severely distorted waveform conditions which occur due to harmonics in the system.

     

    Features
    • Class 1.0s accuracy as per IS13779
    • Class 0.5 accuracy also available
    • Microcontroller based
    • Display: 16 x 1 LCM (Entity), 16x2 LCM with dual source(Infinity), 16x1 LCM without dual source(Infinity).
    Optional
    • RS-485 Communication port with MODBUS-RTU protocol.
    • Dual source measurement (EB & DG) optional available.
    • Whole current models for 32A and 50A available.


    Parameter
    Type Name Statistics
    InputSupplyThree Phases and Neutral of a 3P4W system / Three Phases of 3P3W system.
    VoltageDirect Voltage Input: Up to 300V L-N or 500V L-L Burden: 0.5VA
    CurrentSecondary Current Input: 5A or 1A (To be specified at the time of Ordering)
    CT Primary: Site Selectable
    Range of Reading: 0 - 5000A
    Burden : <1.0VA
    Overload (Through CT): 5A CT = 6A RMS Continuous
    1ACT = 1.2A RMS Continuous
    (Whole Current): 120% of Imax continuous.
    Auxiliary Power SupplyOperating Voltage for SMPS : 80VAC-480VAC, 50-60Hz.
    Comm.RS485 PortSupporting MODBUS-RTU protocol. (Infinity).
    MeasurementEnergyTotal ActiveEnergy (KWh)Range of Reading: 0 to 9999999.9 KWh
    Accuracy: 1.0S as per IS13779.
    MiscellaneousDimensionsBezel96 X 96 mm
    Panel Cutout92 X 92 mm
    Depth of installation55 mm
     Operating temp0°C to 60°C
     Weight0.30 Kg. (Infinity), 0.264 Kg. (Entity)
     Min.Operating Current0.4% of CT primary.
     Dual Source SensingBy presence or absence of 230VAC across two terminals can be looped.







    Share your requirements for a quick response!
    Tell us what you need?

    Looking for Entity Digital Energy Meters?

    Quantity
    Seller Contact Details
    To list your productBoost Your Business Visibility WorldwideRegister Now
    To list your productBoost Your Business Visibility WorldwideRegister Now
    Waiting for permission
    To search by voice, go to your browser settings and allow access to microphone

    Allow microphone access to search with voice