Contact SupplierHigh conductivity annealed stranded copper conductors to SANS 1411 Part 1. Insulated with PVC and skin coloured in plain colours to SANS 1411 Part 2. Cable is manufactured to SANS 1507 Part 2.
INSTALLATION INFORMATIONFor the wiring of Industrial Buildings, Housing, Control Panels it will be easier to pull through conduit, than standard housewire particularly on long and difficult runs.
PROPERTIESA specially developed low friction PVC compound which is used in the insulation of House wire for supply to the South African market.
The decreased coefficient of friction is the result of the migration of the slip additives to the cable surface due to the defined incompatibility of the slip additive with the polymer. (“Slip is a term used to describe the sliding of parallel film surfaces over each other or the sliding of film surfaces over.
The following benefits are relevant :
Cable Size | Nominal Stranding No. x Diameter | Approx Overall No. x Diameter | Current Rating | Conductor Resistance @20°C Maximum | Approx1ø Volt Drop | Approx Cable Mass Per 100m Coil | |
| (mm2) | (mm) | (A) | (W/km) | (mV/A/m) | ()kg | ||
| 100V | |||||||
| 1 | 1/1,12 | 2,25 | 12 | 18,1 | 44 | 1,45 | |
| 1,5 | 1/1,40 | 2,45 | 17 | 12,1 | 29 | 1,65 | |
| 600/1000V | |||||||
| 1 | 7/0,42 | 3,05 | 17 | 18,1 | 44 | 1,75 | |
| 1,5 | 7/0,53 | 3,35 | 21 | 12,1 | 29 | 2,25 | |
| 2,5 | 7/0,68** | 3,65 | 27 | 7,41 | 18 | 3,25 | |
| 4 | 7/0,86** | 4,55 | 38 | 4,61 | 11 | 5,25 | |
| 6 | 7/1,05** | 5,05 | 47 | 3,08 | 7,3 | 7,05 | |
| 10 | 7/1,38** | 6,05 | 64 | 1,83 | 4,4 | 11,15 | |
| 16 | 7/1,76** | 6,95 | 85 | 1,15 | 2,8 | 16,75 | |