Company Information
Ask for more detail from the seller
Contact Supplier| Voltage Range Voltage Range | 110VAC ± 5 % ~ 300 VAC ± 5 % | |
| Frequency Range | 40Hz ~ 70 Hz | |
| Phase | Single-phase with ground | |
| Power Factor | ≥ 0.99 @ full load | |
| OUTPUT | ||
| Output voltage | 200/208/220/230/240VAC | |
| AC Voltage Regulation | ± 1% (Batt. Mode) | |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz | |
| Current Crest Ratio | 3:1 | |
| Harmonic Distortion | ≤ 2 % THD (Linear Load) ; 4 % THD (Non-linear Load) | |
| Overload Capability | 105% ~ 110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal. 110% ~ 130%: UPS shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal. >130%: UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal. | |
| Transfer Time | AC Mode to Batt. Mode | Zero |
| Inverter to Bypass | < 4 ms (typical 2.5ms) | |
| Waveform (Batt. Mode) | Pure Sinewave | |
| EFFICIENCY | ||
| Efficiency(AC Mode/Batt.Mode) | 88% / 83% | |
| BATTERY | ||
| Battery | Type & Numbers | SMF 12V / 9AH x 2 Nos. (IN-BUILT BATTERIES) |
| Charge Current (Min.to Max. Range) | 1A | |
| PHYSICAL | ||
| Physical | Dimension (LxWx H) in mm | 282x145x220 |
| Net Weight (Kgs.) | 9.8 Kgs. | |
| ENVIRONMENT | ||
| Operation Humidity | 20-95 % RH @ 0- 40°C (non-condensing) | |
| Noise Level | Less than 50dBA @ 1 Meter (With fan speed control) | |
| LED/LCD Indication | LCD Display Indications | |
| MANAGEMENT | ||
| Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC | |
| Optional SNMP | Power management from SNMP manager and web browser | |
| Warranty | One Year |