Contact Supplier| Nominal Voltage | 208VAC/220VAC/230VAC | |
| Frequency | 40 Hz~55Hz @ 50 Hz system | |
| Acceptable Voltage Range | 165 ~285 VAC | |
| OUTPUT | ||
| Nominal Voltage | 208VAC/220VAC/230VAC | |
| Voltage Regulation | ± 1 % | |
| Frequency Range (Synchronized Range) (Mains Mode) | 45Hz~55Hz | |
| Frequency Range (Battery Mode) | 50 Hz ± 0.1 Hz | |
| Overload Specs (Mains Mode) | 110%- 120% : 30 MIN 120% – 130% : 5MIN >130% : 1 SEC | |
| Overload Specs (Battery Mode) | 110% – 120% : 3 MIN 120% – 130% : 1 MIN > 130% : 1 SEC | |
| Current Crest Ratio | 3 : 1 | |
| Harmonic Distortion | <= 3 % THD (Linear Load) | |
| <= 5% THD (Non-Linear Load) | ||
| Transfer Time | AC to DC | Zero |
| Inverter to Bypass | Zero (Turn OFF / Common Fault) | |
| Bypass to Inverter | < 5ms (Turn ON/ System Recovery) | |
| Waveform (Battery Mode) | Pure Sine wave | |
| EFFICIENCY | ||
| AC Mode | 87.00% | |
| Battery Mode | 91% | |
| EXTERNAL BATTERY | ||
| Recommended Battery Type | DEFAULT: VRLA / SMF BATTERY TUBULAR BATTERY: OK (WITH CHARGER CUT-OFF VOLT ADJUSTABLE FROM LCD DISPLAY) | |
| Numbers | 16 | |
| Charging Current (Max.) | Default: 8A±10%; Max: 2A, 4A, 8A (Adjustable) | |
| Charging Voltage (Default) | Boost Voltage : 224Vdc +-1%, 14.0V/Battery | |
| Float Voltage : 217.6Vdc +- 1%, 13.6V/Battery | ||
| INDICATORS | ||
| LCD | Load Level, Battery Level, AC Mode, Battery Mode, Bypass Mode, and Fault Indicators | |
| ALARM | ||
| Battery Mode | Sounding every 4 seconds | |
| Low Battery | Sounding every second | |
| Overload | Sounding twice every second | |
| Fault | Continuously sounding | |
| PHYSICAL | ||
| Dimension, DxWxH(mm) | 562 x 250 x 830 | |
| Net Weight (kgs) | 62 | |
| ENVIRONMENT | ||
| Operating Temperature | 0~50ºC (Battery life cycle will shorten when temperature is above 25ºC) | |
| Humidity | 0~95% (Non-Condensing) | |
| Noise Level | Less than 50dB @ 1 Meter | |
| MANAGEMENT | ||
| Modbus RS-232/RS485 | Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux and MAC | |
| Dry Contact | 5 Signals: AC Failure, Low Battery, UPS Alarm, Bypass and UPS Fault | |
| Optional SNMP | Power Management from SNMP Manager and Web Browser | |
| Warranty | Two Years |