Contact SupplierSupply voltage
load voltage l+
rated value (dc) 24 v
permissible range, lower limit (dc) 20.4 v
permissible range, upper limit (dc) 28.8 v
input current
from load voltage l+ (without load), max. 80 ma
from backplane bus 5 v dc, max. 80 ma
power losses
power loss, typ. 4.9 w
digital outputs
numberbinary outputs 16
limitation of inductive shutdown voltage to l+ (-53 v)
lamp load, max. 5 w
load resistance range
lower limit 48 ω
upper limit 4 kω
output voltage
for signal "1", min. L+ (-0.8 v)
output current
for signal "1" rated value 0.5 a
for signal "1" permissible range for 0 to 40 °c, max. 0.6 a
for signal "1" minimum load current 5 ma
for signal "0" residual current, max. 0.5 ma
switching frequency
with resistive load, max. 100 hz
with inductive load, max. 0.5 hz
on lamp load, max. 10 hz
aggregate current of outputs (per group)
horizontal installation
up to 40 °c, max. 4 a
up to 60 °c, max. 3 a
vertical installation
up to 40 °c, max. 2 a
cable length
cable length, shielded, max. 1000 m
cable length unshielded, max. 600 m
interruptsdiagnosticsstatus information
alarms
diagnostic alarm no
diagnostic messages
diagnostics no
wire break no
short circuit no
fuse blown no
missing load voltage no
diagnostics indication led
rated load voltage pwr (green) no
fuse ok fsg (green) no
galvanic isolation
galvanic isolation digital outputs
between the channels, in groups of 8
between the channels and the backplane bus yes; optocoupler
isolation
isolation checked with 500 v dc
connection method
required front connector 20-pin
dimensions
width 40 mm
height 125 mm
depth 120 mm
weight