Contact Supplierenterprise standard: equivalent to gb/t 12706-2008 and iec 502-2004.
usage
this product is suitable for use in rated ac voltage (u0/u) 0.6/1.0 kv and 1.8/3 – 8.7/10 kv system transmitting and distributing circuit.
property for use
a. it is far better than all property targets of pvc insulated power cable and has over come the short comings of physical and chemical cross-linkage, and completely reaches of surpasses gb and iec technical property value.
b. the allowed max. Cable conductor work temperature is 90℃ , urgent excess work temperature is 130 ℃ for  short circuit ( 5s) , max. Conductor temperature is 250 ℃ .
c. the environmental temperature for laying cable should be not less than 0℃ . If laying under 0℃, the cable should be preheated .
d. the cable bend radius for single core should be not less than 16 times of overall cable diameter ; for multi-core cable , not less than 12 times of overall cable diameter.
e. the current-carrying capacity is large and not limited by drop during laying.