Contact Supplier| MAINS INPUT | |
| Voltage | 415 V +10% – 15% 3Ph 3W |
| Frequency | 50 Hz ±10% |
| DC BUS | |
| DC Voltage Range | 305V to 482V |
| Maximum DC Bus Ripple (without battery) | 2% RMS |
| Max DC Bus Ripple (with battery) | 1% RMS |
| OUTPUT | |
| Nominal AC Voltage | 110/115/120/220/230/240 V |
| Load Power Factor – Rated | 0.8 |
| Load Power Factor – Range | 0.6 to Unity |
| Voltage Regulation | |
| Steady State | ±1% |
| 100% Step Load | ±5% typical |
| Recovery Time to 98% | < 20 ms |
| Over Load | |
| 110% | 3600 Seconds |
| 125% | 600 Seconds |
| 150% | 60 seconds |
| Branch Fuse Clearing Ability | 30% of UPS rated current (fast acting semiconductor protection fuse)10% of UPS rated current (slow acting fuse)) |
| Frequency | 50 Hz |
| Bypass Synchronization Window | ±1% to 6% (Field Programmable) |
| Internal Oscillator | ±0.1% |
| Slew Rate | 1 Hz/Sec |
| Total Harmonic Distortion | |
| Linear Load | <2.5% |
| Nonlinear Load (CF 3:1) | <5% |
| OPERATING CONDITIONS | |
| Ambient Temperature | 500C |
| Altitude | 1000 Meter From MSL |
| Humidity | 95% Non-Condensing |
| Atmosphere | Non Corrosive, Dust Free, Freely Ventilated |
| Audible Noise @ 1metre from Panel Front | 55 dBA to 75 dBA (depending on system rating and Configuration) |
| ENCLOSURES | |
| Construction | CRCA Steel Sheet |
| Protection Class | |
| Finish (Powder Coated) | RAL 7032 (Other Colours Optional) |
| Ventilation | Forced Air (Internal Fans) |
| Cable Entry | Bottom (Top Optional) |