The SMPS Battery Charger is serving the twin purpose of supplying the DC load and simultaneously charging 70 AH, 110 Volts SMF lead acid batteries.
Input
Rated operating Voltage : 3 Phase, 415 Volts 5%
Limiting operating Voltage : 3 Phase, 415 Volts 15%
Limiting operating current : 20 Amp
Output
Rated output Voltage : Function of (Battery voltage, battery current, temperature of the battery)< 135 V
Battery charging current : 20 Amps
Maximum Output Current : 50 Amps
Maximum load current : 50 Amp minus battery charging current
Maximum output power : 130 VX50 Amp = 6500 watts
Ripple Current : V