1 Products availableWe offer a complete product range of Pocket Size Gas Detector, Refrigerant Gas Detector, Multi Gas Detector, Multi Gas Detector (Metrex 3) and Multi Gas Detectors (G460)
Specifications
Portable Gas Detector | |
---|---|
Function | Detecting flammable gases |
Sensor Type (detection Method) | Catalytic bead/Diffusion |
Detectable gases | LPG, Butane, Propane, CNG and Methane gas |
Range | 0-10,000ppm |
Display | Green LED Power on yellow LEd Low alarm 1000-2000ppm Red LEd High Alarm 3000ppm |
Alarm type | Buzzer 80 dB at 50 cm |
Duration of use | Max 10 hours |
Temperature | -10 to +50 deg c |
Humidity | 95% Rh or lower, non-condencing |
Weight | 25g(without battries) |
We are one of the highly acclaimed Manufacturers and Suppliers of Refrigerant Gas Detectors in Mumbai (India). The Refrigerant Gas Detectors, offered by us, are powerful tolls for pin point gas leak protection. The Refrigerant Gas Detectors are fabricated using the best grade raw materials and the latest technology. Salient Features Of Refrigerant Gas Detector
Specifications
Model | XP 704 |
---|---|
Gas Detected | R-22, R-123, R-23, R-32,R134a, R-142b, R-404A, R-407A, R- 407C, R-407E, R-410A, R-507A, R-290, R-600a, R-707 |
Sampling Method | Automatic suction with built in micro air pump |
Detection Principle | Hot wire semiconductor |
Minimum detectable Leak rate | 5ppm |
Minimum Detectable Concentration | 2.1 x106 pa m3 /s, 2.8g/ year leak |
Response time | 10 sec. or less |
Detection Indication | Intermittent buzzer and flashing lamp |
Power Source | 4xAA (R6) dry cells |
Battery Life | Approx. 3 hours by manganese dry cell Approx. 9 hours by alkaline dry cell |
Operating Temperature | 0o c to 40o c |
Weight | Approx. 400g |
Dimensions (W x H x D) | 68 x 155 x 32 mm |
Standard Accessories | Probe with filter/moisture trap, Check gas, Filter element. Soft case, 4x AA (R6) manganese dry cells, Spare filters |
Optional Accessaries | Battery charger (Nicd only), Ear phone etc |
The company is a major Manufacturer and Supplier of Multi Gas Detector (Metrex 3) in Mumbai. The Multi Gas Detector (Metrex 3) is one of the widely used professional equipment meant for the localization and detection of gases like methane and propane. Effective for use in aerial as well as underground pipelines, the Multi Gas Detector (Metrex 3) can be combined with as many as six sensors and is effective for detecting toxic gases, ethane, hydrocarbons, hydrogen, helium, odorants and devices like Bluetooth and GPS antenna. Completion Accessories For Multi Gas Detector (Metrex 3)
Optional For Multi Gas Detector (Metrex 3)
Multi Gas Detector (Metrex 3) Probes
Control System For Multi Gas Detector (Metrex 3)
Documentation For Multi Gas Detector (Metrex 3)
Specifications
METREX 3 | 01 | 02 | 03 | 04 | 05 | 08 | 06 | 09 | 07 | 10 |
---|---|---|---|---|---|---|---|---|---|---|
0-100% *LEL | X | X | X | X | X | X | X | X | ||
0-100%VOL *CH4 | X | X | X | X | X | X | X | X | ||
0-10.000 PPM *CH4 | X | X | X | X | X | X | X | X | ||
0-30% O2 | X | X | X | |||||||
0-2.000 PPM CO | X | X | X | |||||||
0-10.000 PPM H2 | X | |||||||||
0-5% VOL H2 | X | |||||||||
0-100PPM H2S | X | |||||||||
0-100 PPM 5% VOL He | X | |||||||||
Ethane | X | X | X | X | ||||||
THT | X | |||||||||
TBM | X |
Features
Compact and Rugged designThe durable G460 continuously measures and displays readings for up to six gases at the same time. The robust and watertight (IP 67) housing incorporates a built-in concussion proof boot to survive the toughest environments. Easy OperationA single on-off button is all it takes for normal day-to-day operation. A simple three button interface provides access to advanced setup options. Calibration adjustment is completely automatic; just attach the calibration adapter and apply gas. The instrument automatically makes adjustments and retains the three most recent calibration dates for each sensor. Motorized Sampling PumpThe Motorized Pump includes a built-in slide-shutter switch that permits operation in either diffusion or sample-draw mode while the pump is attached. The easily attachable pump is powered by its own battery pack that provides 20 hours of continuous sampling from up to 100 feet away. Widest Range of SensorsG460 detectors are available for use with a wide range of long-lasting, interchangeable smart-sensors for LEL, O2, H2S, CO, NH3, SO2, CL2, PH3, NO and H2. Infrared (NDIR) sensors for the direct measurement of CO2, and photoionization detectors (PID) for the measurement of volatile organic chemical (VOC) hazards are also available. Lifetime WarrantyThe G460 carries a lifetime warranty on non-consumable components and a two-year warranty on consumable components. O2, LEL, H2S, CO and COSH sensors carry a full three-year warranty against failure. Datalogging / Event Logging StandardThe G460 automatically stores complete results for the most recent 55 hours of monitoring. Any periods during which readings exceed the alarm thresolds are stored as "events" in the permanent on-board memory. Downloading logged information to generate reports and graphs of your monitoring results is easy and automatic with a simple to use data transfer cable. Interchangeable Battery PacksInterchangeable alkaline and rechargeable (NiMH) battery packs provide up to 25 hours of continuous operation. The drop-in cradle charger fully charges a depleted battery pack in less than 4 hours. The cradle includes LEDs to indicate fast charge / trickle charge status. Built-in "Flash Light" LEDsG460 detectors can be equipped with built-in high intensity "flash light" LEDs. Innovative Easy-to-Read Display and AlarmsThe large, easy-to-read, three-color display changes color to indicate the severity of the alarm; the backlight color changes from green for "OK" to orange or red for an alarm. The loud audible alarm (103 dB at 12"), built-in vibrator and bright 360º LED alarm indicators alert users to hazardous conditions. The backlit display can be "flipped" 180º or "zoomed" at the push of a button for even easier readind.
Technical Data
Dimensions | 2.5 x 4.3 x 2.0 inches (90 x 140 x 55 mm) |
---|---|
Weight | 10 oz. (280 g) with O2/LEL/CO/H2S sensors, 14 oz (380 g) with IR CO2 or PID |
Power | 2 AA alkaline batteries or rechargeable NiMH pack |
Operation Time | Up to 24 hours of continuous operation with LEL and toxic sensors; up to 10 hours with IR CO2 or PID sensors |
Charging Time | Less than 4 hours |
Ambient Conditions | -4º to + 122º F (-20º + 55º C); 5-95% RH |
Intrinsic Safety | IECE x/ATEX II 2G Ex la dc IIC T4 c-CSA-us Class 1, Div I, Groups A, B, C, D CE (EN 89/336/EWG |
Features
Options
Specifications
Gas Detected | Combustible gas (methane or isobutane) | Oxygen | Hydrogen Sulfide | Carbon Monoxide |
Detection Principle | Catalytic combustion | Galvanic cell | Electrochemical cell | Electrochemical cell |
Detection Range | 0-100%LEL (1%LEL resolution) | 0-25.0vol% (0.1vol% resolution) | 0-30.0ppm (0.5ppm resolution) | 0-300ppm (5ppm resolution) |
Indication Accuracy *1 | ±10% of full scale value | ±0.5vol% | ±5% of full scale value | ±10% of full scale value (1-150ppm) |
Alarm Set Value | 1st stage: 10%LEL 2nd stage: 25%LEL | Lower limit: 18.0vol% Upper limit: 25.0vol% | 1st stage: 10.0ppm 2nd stage: 20.0ppm | 1st stage: 50ppm 2nd stage: 150ppm |
Alarm Accuracy *1 | ±25% of Set Value | ±1.0vol% | ±30% of Set Value | ±30% of Set Value |
Response Time | 30s or less (90% response) | 20s or less (90% response) | 30s or less (90% response) | 30s or less (90% response) |
Concentration Indication | 3-digit LCD (When two gases are selected, the concentrations are displayed alternately in every five seconds.) | |||
Alarm Indication | 1st stage: Intermittent buzzer and LCD "AL" part fl ashing 2nd stage: Continuous buzzer and LCD "AL" part lighting | |||
Power Source | 3xAA (R6) alkaline dry cells | |||
Battery Life *2 | Combustible gas combined : Up to 48 hours (by alkaline cells); Battery remaining indication : 4-level display in LCD "BATT." part Combustible gas NOT combined : Up to 2000 hours (by alkaline cells); Low battery : Intermittent buzzer and LCD "BATT." part flashing | |||
Additional Functions | Gas concentration peak hold function, Auto-zero function (except oxygen), Earphone terminal. | |||
Explosion-Proof Structure | Ex iad IICT4 (with combustible gas) Ex ia IICT4 (without combustible gas) | |||
Operating Temperature Range | -10 to 40ºC | 0 to 40 ºC | ||
Dimensions/Weight | W56xH121xD32mm (excluding protrusions) Approx. 165g (excluding batteries) |
Gas Detected | Diffusion | Extractive |
---|---|---|
Combustible gas | XA-911 | XP-911 |
Oxygen | XA-912 | XP-912 |
Hydrogen sulfi de | XA-913H | XP-913H |
Carbon monoxide | XA-913C | XP-913C |
Combustible gas/Oxygen | XA-927 | XP-927 |
Combustible gas/Hydrogen sulfide | XA-924H | XP-924H |
Combustible gas/Carbon monoxide | XA-924C | XP-924C |
Oxygen/Hydrogen sulfide | XA-925H | XP-925H |
Oxygen/Carbon monoxide | XA-925C | XP-925C |
Hydrogen sulfi de/Carbon monoxide | XA-926 | XP-926 |
Combustible gas/Oxygen/Hydrogen sulfide | XA-936H | - |
Combustible gas/Oxygen/Carbon monoxide | XA-936C | - |
Combustible gas/Hydrogen sulfi de/Carbon monoxide | XA-937 | - |
Oxygen/Hydrogen sulfi de/Carbon monoxide | XA-938 | - |
Combustible gas/Oxygen/Hydrogen sulfi de/Carbon monoxide | XA-948 | - |
Features
List Of Detected Gases
Type | Gas | Full Scale |
---|---|---|
XDS-7NH | NH3 | 100 ppm |
XDS-7SH | SiH4 | 25 ppm |
XDS-7DC | SiH2CL2 | 25 ppm |
XDS-7AH | AoH3 | 250 ppb |
XDS-7PH | PH3 | 1ppm |
XDS-7BH | B2He | 500ppb |
XDS-7SE | H2So | 250ppb |
XDS-7GH | GeH4 | 1ppm |
XDS-7CL | Cl2 | 5ppm |
XDS-7CF | ClF3 | 1ppm |
XDS-7HC | HCl | 25ppm |
XDS-7HF | HF | 10ppm |
XDS-7HB | HBr | 10ppm |
XDS-7NO | NO | 100ppm |
XDS-7HS | H2B | 50ppm |
XDS-7CO | CO | 250ppm |
XDS-7DS | Bi2H2 | 25ppm |
XDS-7F2 | F2 | 5ppm |
XDS-7OZ | O3 | 1ppm |
Specifications
Model | XPS-7 |
---|---|
Detection Principle | Electrochemical cell |
Gas Detected | Semiconductor manufacturing gases |
Gas Sampling Method | Extractive |
Detection Range | Depends on the specific action |
Resolution | 1/100 of full scale |
Indication Accuracy | 10% of full scale |
Alarm Mode | 2nd stage alarm type |
Alarm Indication | Intermittent buzzer, flashing lamp |
Response Time | 60 or less (60% response) |
Operating Temperature | 0 to 40oC |
Power Source | 4 x AA Alkaline dry cells(*2) or an AC adaptor |
Battery Life (*2) | Up to 12 hours (by alkaline dry cells at 20oC without alarm) |
Dimensions | W 62 x H 150 x D 128 mm (excluding protrusions) |
Weight | Approx. 1.3 kg |
Standard Accessories | Gas sampling hose with probe, Shoulder strap, 4 X AA alkaline dry cells, Spare filters |
Optional Accessories | AC adaptor (100 VAC/B VDC), Sensor Stocker, Log data collection kit |
Features Simple and reliable gas detector
Cost effective and easy installation
Rugged and compact Design
Environmentally-friendly product
Specifications
Model | KD-12 |
---|---|
Corresponding Sensor Type | Hot wire semiconductor type (KD-12A) or Catalytic combusion type(KD-12B) |
Sampling Method | Diffusion |
Alarm Accuracy |
|
Alarm Delay |
|
Waring Display |
|
External Output | Gas concentration analog signal (direct linear reading of concentration)
|
Gas Concentration Display | Four- digit digital LED display (direct linear reading of concentration) |
Operation | At 4 points of magnetic switches |
Cable Connection | Screw-less terminal blocks |
Explosion-proof | Ex d IIC T5 (Japan TIIS), Ex d IIC T6 (China Explosion-proof inspection) |
Degree of protection | IP65 (internal instrument) |
CE Marked | Complied with CE Directive 89/336/EEC,92/31/EEC, 93/68/EEC |
Applicable Cable | Cable outer diameter (10 to 13 mm dia.)
|
Temperature and Humidity range |
No radical temperature or humidity changes and no condensation |
Power Supply | 24V DC (18 to 30V DC) |
Power Consumption | 3 W or less |
Dimensions | 158(W) X 116 (H) X 68 (D) mm (excluding protrusions) |
Weight | Approx. 1.2Kg |
Specifications
Model | XP 311± A |
---|---|
Detection Principle | Catalytic Combustion sensor |
Minimum Detectable Leak Rate | 0.5%LEL. |
Measuring Range | 0 to 10% and 0 to 100% LEL |
Calibrating Gas | LPG (iso-butane) or methane. Calibration for other specific gases is available on request. |
Accuracy | + 5% of full scale reading |
Response Time | Within 3 seconds (90% of final readind). |
Alarm Style and Preset Point | Intermittent tone and flashing lamp 20% LEL. preset, but available at other point on request.( not in XP 311). |
Operating Temperature | -20o to +50o (-4oF to + 122oF). |
Power Source | Size AA dry cell batteries (1.5 V x 4 pcs). |
Battery Life | 100 intermittent tests of 3 minutes duration each or 4 hours for continous operation using dry cell batteries. |
Dimentions | 190 mm x 84 mm x 40 mm. |
Weight | 700 gr. (1.5 lbs.). |
Standard Accessories | Non-conductive probe with filter/ moisture trap. 1 meter long sampling hose. Carrying case with shoulder strap. Set of four size AA dry cell batteries. Two filter elements. |
Optional Accessaries | Sampling tube 5 m long or as required. Floating Probe with float and filter / moisture trap. Telescopic probe. Flexible probe. Remote alarm signal unit (BEZ -1) with 10m long cable. |
Features
Compact Area MonitorsmG-4000 monitors are compact detection instruments that accurately measure combustible gases, toxic gases and oxygen levels. Three Alarms, in-built hysteresis, universal power input, variety of Audio-visual alarm devices, 3 digit LED display, 1 digit Ch. No. display, variable ranges LEL, Vol., ppmall these make this Monitor a power house of gas monitoring systems. Simple and effectiveThe unit accurately displays measured gas concentration on a large 3 digit LED display. Compact and simple design facilitates easy doit- yourself type installation. Pre-calibrated Sensors allow direct commissioning without need of skilled manpower. Monitor is equipped with onboard relays for three alarm points. It also has one sensor fault relay output. These relays can be used to driveexternal devices like strobes, fans, voice alarms, auto-dialers, etc.
Technical Data
Technical Data
Ordering Details | |
---|---|
Gas | |
Range & unit | |
Sensor : Local / Remote | |
Optional Accessories | Pl. specify |
Detection Principle | Catalytic Comb., Electrochemical Infra-red |
---|---|
Detection Method | Diffusion |
Response Time | T90 < 30 sec. (depending on gas) |
Expected Sensor Life | 2-8 yrs. (depending on gas) |
Display | 3 digits LED for Gas Concentration 1 digit LED for Channel Number Pilot, AL1,AL2, AL3 and Fault LEDs |
Power Supply | Univ. 100-250 VAC/24VDC |
Relays | 3 Alarm points, 1 fault- pot. free 2A @250VAC, Form C |
Temperature Range | 0 to 50°C |
Humidity Range | 5 to 95% Rh |
Housing | ABS box with transparent lid |
Weight | < 2Kgs. |
Dimensions | 241 x 285 x 145mm (H x L x D) |
Enclosure Protection | Weather proof IP 65 |
Accessories | Voice Alarm, Indoor/Outdoor Hooter- Flashers, Suction Unit, Battery Back-up, Suction Detector Units |
Features
Features
Features
Features
Features
Features
Technical Specifications
Sensing element | PELLISTORS, Industrial grade Electrochemical Cells, INFRARED sensor |
---|---|
Measurement range | 0-100% LEL, ppm for toxic gases, %vol. for CO2 |
Power supply | 12- 24 Vdc +/- 15% |
Consumption at 12Vdc | 90 mA (nominal); 130 mA (max) |
Visual indications | Flashing LED (standard); 3 red LED for Alarm levels, yellow for Fault and green for Power supply (display version). |
Display characteristics (Display version only) | 4 digit, 7.5 mm high, 7 segment display |
Analog output | 4-20 mA (200 Ω) |
Serial Output (optional) | Serial RS-485 MODBUS protocol |
O/C or relay outputs (optional) | Open collectors or relay optional boards |
Precision | 1.5% full range or 10% reading |
Repeatability | +/- 5% full scale |
Warm-up time | 5 minutes |
Stabilization time | < 2 minutes |
Response time | < 15 sec. T50; < 25 sec. T90 (flammable gas with Pellistor) |
Storage temperature | -25 / + 60oC |
Operating temperature | -10 / + 60 oC (flammable gas version) |
Relative humidity | 20-90 % Rh / 40 o C |
IP rating | IP65 (Exd version); IP55 (Exn version) |
Operative pressure | 80-110 KPa |
Air velocity | < 6 mS -- check unit |
Weight | Exd : 900 gr. Blind Exn: 800 gr Blind Exd : 900 gr. Display Exn : 700 gr display |
Dimension | Exd : L.106, H. 160, D. 80 mm Exn : L.106, H. 180, D. 65 mm |
Orientation | The detector must be mounted with sensor head downward |
Reference Norms | EN60079-0 EN60079-1 EN60079-15 EN61241-0 EN61241-1 (Electrical Apparatus for Explosive Atmospheres). EN 61779-1/4 (Performance) |
Certificates | CESI 01ATEX053 (Exd version) CESI 03ATEX339 (Exn version) CESI 02ATEX084 (Exd + performance) CESI 04 ATEX106 (Group I) |
Note : Indications & Magnetic Programming Features are available with Display Version only. Some of the features are optional. |
Features
Features
Features
Features
Specifications
Model | XS-2200 |
---|---|
Gas Detected | Hydrogen Sulfide (H2S) |
Detection Principle | Electrochemical cell |
Sampling Method | Diffusion |
Detection Range (Service Range) | 0-30.0ppm (30.1-100ppm) |
Resolution | 0-35.0ppm : 0.1ppm 35-100ppm : 5ppm |
Indication Accuracy *1 | Within± 0.5ppm ± 1digit |
Alarm Set Value 1st stage /t2nd stage |
10.0ppm 15.0ppm |
Response Time *2 | 30s or less |
Display Mode | LCD (Manual backlight) |
Alarm Mode | Buzzer sounds, flashing red light, vibrator |
Functions | Remaining battery level, peak hold, memory of peak value alarm functions except gas alarm ( sensor malfunction, remaining battery level, air adjustment malfunction ) |
Operation Temperature | -10o to 40o C, 30-85% RH (non-condensing) |
Operating Air Pressure | Air pressure ±10% |
Power Source | 1 X AAA alkaline dry cell |
Battery Life *3 | Up to 5,000 hours (at 20ºC with less than 5ppm) |
Dimensions | W65 X D22 X H64mm (excluding protrusions) |
Weight | approx. 75g (including battery) |
Standard Accessories | 1 x AAA alkaline dry cell, 1 X safety pin adaptor (with fixing screw) |
Features
Specifications
Model | XC-2200 |
---|---|
Gas Detected | Carbon Monooxide (CO) |
Detection Principle | Electrochemical cell |
Sampling Method | Diffusion |
Measuring Range (Service Range) |
0-300ppm (300-2,000ppm) |
Resolution | 0-350ppm: 1ppm / 350-2,000ppm:50ppm |
Indication Accuracy *1 | Within± 30ppm |
Alarm Set Value | 50ppm (first stage), 150ppm (second stage), 150ppm h(time weighted average) |
Response Time 2+ | 30 secs.or less (90% of final reading) |
Display Mode | LCD (Manual backlight) |
Alarm Mode | Buzzer sounds, flashing red light, vibrator |
Functions | Remaining battery level, peak hold, peak value memory, readout of time weighted average, alarm functions except gas alarm (time weighted average value, sensor malfunction, remaining battery level, zero-adjustment malfunction), gas calibration, gas concentration |
Operating Temperature | -10o to 40o C, 30-90% RH (non-condensing) |
Operating Air Pressure | Air pressure ±10% |
Power Source | 1 X AAA alkaline dry cell |
Battery Life *3 | Up to 5,000 hours (at 20ºC with less than 20ppm) |
Dimensions | W65 X D22 X H64mm (excluding protrusions) |
Weight | Approx. 75g (including battery) |
Standard Accessories | 1 x AAA alkaline dry cell, 1 X safety pin adaptor (with fixing screw) |
We offer SA 150, which can be used to detect various types of combustible and toxic gases. SA 150 is a quality multi-gas detection system, which can be used to detect and measure various gases, including - CO, H2S, C2H4O, COCl2, NH3, COCl2, NO, SiH4, SO2, and more. SA 150 comes in three different specifications, i.e. - with a built in internal buzzer, with a built in external buzzer and with a remote buzzer. The system comes complete with all essential components of a gas detection system, such as - gas sensor, electronic amplifier, alarm unit, visual alarm indicator and audio alarm annunciator.
Features
Specifications
Target Gas | 150 Gases such as LPG, CNG, Natural Gas, Ammonia, Chlorine, H2S, O2, Ozone etc. |
---|---|
Pilot Lamp | Green LED, if OFF it indicates either power failure or the unit is in-operational. |
Alarm Lamp | RED, LED, if on it indicates that the gas concentration has exceeded the alarm set value |
Alarm Set Limit | Fraction TLV and LEL |
Warm-up time | Each unit, based on sensor used has a time delay after power up during which the unit warms up to stable condition. The unit can not detect the gas concentration properly during this time. Power down storage duration and storage conditions also affect the warm up time. This time can vary from few minutes to several hours. |
Audio Alarm | When the gas concentration exceeds the set limit and alarm lamp is ON, the audio alarm is sounded. Some units are provided with a time delay (factory set) for the audio to be operational. This filters short duration gas leaks and false alarms. This delay is generally set below 30 sec. |
Response Time | Each sensor has a response time for which the gas must be present to get detected by the sensor. |
Power Supply | Generally all these units work on AC 230 V 10%, 50 Hz |
Mounting Style | Wall or Panel Directly. Other methods through accessories |
Digital Display | Some models are provided the large LCD display which continuously shows, the gas concentration as sensed by the sensor ` |
Size | 200 mm x 120 mm x 80 mm |
Weight | <900 gms |
Superior in quality and performance, FF-400 is a high performance gas detection equipment that can be designed as per requirement. FF 400 is a precision engineered gas detection equipment that comes with a field replaceable unit complete with gas sensor, terminal / junction box, gland and more that can be designed as per requirement. FF-400 is very easy to use and install and the superior design ensures interferences from electric noise, temperature, humidity and pressure.
Features
Monitor / Alarm Unit
Capacity | Upto 10 channels |
---|---|
Power Supply | Universal AC input 100-250 AC, 50-60 Hz |
Power Consumption | 1.5W/ channel-normal operation |
Output | Driver for Auto shut-off valve, Suction Pump, Annunciation Panel etc. |
Enclosure | ABS, IP65 weather-proof |
Indication | Alarm-1 Red LED/ Channel Pilot-1 Green LED |
Warm up time | <5 minutes |
Response time | Very quick (depends upon target gas) |
Size (WxHxD) | 250x250x150 (mm) |
Alarm Type | Auto-resetting |
Alarm level | Factory preset-PPM, fraction of LEL/ TLV |
Operating Temp. | -100C to 500C |
MG 1000 is a high sensitivity fixed gas Detectors that offers a flexible combination of relays and / or external drive outputs. MG 1000 is a micro controller based multi, point gas monitoring and alarm system that can accept inputs for different types of gases, including combustible, oxygen, ozone, carbon dioxide etc., and more. The equipment provides flexible combination of relays and / or external drive outputs, depending on the application. Available at competitive prices, this is a compact low power system with unmatched reliability.
Gas Monitoring System
Indicator / Alarm Unit
Type | Micro controller based module |
---|---|
Capacity | 2 channel in 1 module |
Indications | For each channel independently Digital display 0 to 99% or Bar Graph (10 segment) 0-100% Warm (Low level) - Red LED Alarm (High level) - Red LED Fault - Yellow LED Pilot - Green LED (Common) |
Controls | Four Magic Push buttons to review and program all parameters |
Programmable Functions | For each channel independently Warm (Low level alarm) set point Alarm (High level alarm) set point Skip Alarm delay common for 2 channel |
Calibration | Software based tamper proof, no tools required, zero and full-scale can be set independently |
Outputs | Warm, Alarm, Fault |
Specifications
Detected gas | LP gas | Natural gas |
---|---|
No. of connectable detectors | KD-5G, KD-5T,GD-1B,GD-3L | KD-5M |
Alarm Type | Flashing red lamp (illuminated after alarm shut off), alarm sound, auto- restore type(can be set to self- retention function using DIP switch) |
Alarm volume | 70dB/m min. |
Alarm shut off | By pressing a button |
Malfunction display | Flashing yellow lamp |
Display of alarm unit operation | Illuminated green lamp |
Power source | AC100V to AC220V, 50/60Hz (Terminal block type) |
Power consumption | Approx. 5W when monitoring (maximum) Approx. 10 W during alarm (maximum) |
External output |
|
Operating Temperature Range | -10o to 40oC |
Dimensions / Weight | W138 x H230 x D45 mm / Approx. 480 g |
Accessories | Inspection gas, Mounting plate, Wood screws, Crimp terminals, hex wrench |
This system has a wall mount case incorporating indicator units and an alarm unit of the V Series/V2 Series
Outline
Features
Specification
Item / Model | V-810 |
---|---|
Gas Detected and Detection Range | As per specification |
Gas Concentration Indication | LCD bar-graph level meter |
Alarm Set Volume | Adjustable within the detection range(Except hexane for which 0.5ml is the alarm set value) |
Alarm Accuracy | Combustible gas:+25% of an alarm Set Value Toxic gas: +30% of an Alarm Set Value Oxygen: +1.0vol% of an Alarm Set Value(Conforms to JIS T 820) |
Alarm Indication |
|
Contact Output | Indicator unit (individual alarm): 1st stage(1a), 2nd stage(1a), 1 A@ 100V Ac (resistance load) Alarm unit (collective alarm): Alarm 1(1c), Alarm 2(1c),1A@100V AC (resistance load), Trouble (1a), Buzzer (1a) |
External Output *1 | 4-20mA, 0-10mV,1-5V (option), RS-232C output (option) |
Operating Temperature Range | -10oC to 40oC |
Power Source | 100-110V AC+10%, 200/220V AC+10%, 24V DC+10% |
Power Consumption | Diffusion type: (25+5n)VA, suction type: (25+10n)VA (n is the number of detection points) |
Others |
|
*1 V2 series are not capable of 0-10mV output.
Simple, large button operation, analog gas reading at a glance makes the XP-311II the easiest detector to use on the market.Based on the proven and successful previous version, the XP-311II is designed to be more affordable.It is the perfect detector to meet the safety.monitoring requirements of many industries. Features :
Features
Application
Also suitable for use in oxygen deficiency hazard area for continuous monitoring of oxygen concentration and for safety ensuring during construction.
Specifications
Model | KS-60 |
---|---|
Gas Detected | Oxygen |
Detection Range | 0-25.0vol%, or 0-50.0vol% |
Gas concentration Indication | LCD digital(0.1vol%resolution) |
Alarm Set Value | 1st stage: 19.0vol%, 2nd stage: 18.0vol% (factory defaults) |
Alarm Indication | Gas alarm (1st / 2nd stage); Red LED flashing (AL1/Al2) Intermittent buzzer (when the buzzer is on) |
External Output | Gas concentration analog output : 4-20mA DC Gas alarm contact (for 1st / 2nd stage) : 1a |
Operating Temperature/Humidity | 0oC to 40oC, 30-85%RH |
Power Source | 24V DC + 10% |
Power Consumption | Approx. 2 W |
Dimensions | W82 x H154 x D30mm (excluding protrusions) |
Weight | Approx. 500g |
Installation | Wall mount |
Exterior Color | Munsell N7.0 |
Other function | Peak hold, Maintenance mode, Low battery alarm (when using the battery unit) |
Technical Specification
Inputs | Upto 8 analog inputs 4-20 mA |
---|---|
LED indications | Pilot, Al1, Al2, Al3, Fault and Battery Low. |
Display | Backlit Alphanumeric LCD 16character 2 lines |
Relay Outputs | 5 relays NO-C-NC, Gr.AL1, Gr.AL2, Gr.AL3, Gr. Fault, Programmable Aux. |
Electrical Outputs | 16-2 (Al2 & Al2) Al3) per channel for Annunciator Panel-optional |
Operating Modes | Operation, Maintenance, Program |
Power Supply | 220 V AC+/- 10% |
Battery Back-up | Built-in, Time 1 hr to 24 hrs. |
Dimensions | 360 x 225 x 150 mm |
Operating temperature | 0-45 degree C |
Relative humidity | 5-90% non-condensing |
The company is one of the well-established Manufacturers and Suppliers of Segugio Residential Gas Leakage Detectors in Mumbai. The Segugio Residential Gas Leakage Detectors, offered by the company, are widely appreciated for their quality and efficiency. The various models of the Segugio Residential Gas Leakage Detectors are built using the latest technology and the company offers these products at affordable prices.
Features
Specifications
Model | Xp-703D |
---|---|
Detection Principle | Hot wire semiconductor |
Sampling Method | Extractive |
Gas Detected | Semiconductor manufacturing gases (arsine, phosphine, diborane, silane, etc.) |
Minimum detectable Leak rate Minimum Detectable Concentration |
arsinr/t phosphine/t diborane/t silane/t hydrogen AeH3/tPH3/tB2H6/tSiH4/tH2 1.0 X 10-7/t1.5 X 10-7/t0.5 X 10-7/t2.5 X 10-7/t5 X 10-7 Ps M3/s 0.2/t0.3/t0.1/t0.5/t1.0ppm |
Response Time | 10 or less |
Detection Indication | Intermittent buzzer and flashing lamp |
Power Source | 4 X AA (R6) manganese dry cells |
Battery Life | Up to 9 hours by alkaline dry cells (Up to 3 hours by manganese dry cells) |
Operating temperature | 0 to 40oC |
Dimensions | W89 x H155 x D32mm |
Weight | Approx. 400g |
Standard Accessories | Soft case, Probe with filter/ moisture trap, Check gas, Standard attachment, 4 X AA (R8) manganese dry cells, Spare filters |
Optional Accessories | Earphone |
Features
Micro IV - With docking station for quickest calibration, function test and data transfer to a PC
The Micro IV is the state of the art derivative of the well known single gas detector MICRO III. Besides its simple operation and reliable warning the flexible device convinces because of its large memory, an IR interface and the revolutionary docking station.
The event memory saves all important data
The MICRO IV docking station is a trendsetting device management system, which enormously reduces cost of ownership and duration of the calibration. The docking station checks the acoustic and optical alarm functions, device errors, alarm thresholds and response times of the MICRO IV. The bump-test comprises
Up to 6 MICRO IV can be checked for utilizability (bump-test)and be calibrated simultaneously. Simplest operationThe docking station reduces the daily time involved for calibration and function test (bump test) dramatically. Already few calibrations and function checks annually reduce the cost of ownership considerably. The uncomplicated and quick operation in connection with the self-describing traffic lights signals prevent from user mistakes. Due to the compact size the station can be placed almost everywhere without an y problems. No further modules or master stations are necessary. Sampling pumpAn electrical high-performance pump will take samples of gases from mines or tanks. The pump replaces the battery cover and is a fixed part of the instrument with its own power supply. The operation of the pump will have no influence on the operation time.
G450 compact, lightweight and easy handling 4 gas detector measure H2S, CO, O2 and combustibles in ambient air continuously. The device allows intuitive handling with only three soft keys because of the simple menu drive. A large full graphic relevant data. It has the extremely loud audible alarm and bright moving all-round LEDs. Depending on alarm status, the display changes its color from green to orange or red. TLV, TWA and STEL values are also monitored. A vibrating alarm is available optionally. An electrical HD pump with own power supply is attachable. In case of insufficient flow caused by blocked or snapped tubing flow alarm is triggered. The optional loop data logger records gas concentrations and alarms over a period of 50 hours. These data can be transferred to PC for visualization and evaluation. The display can be turned 180º by just pushing a button. This allows an easy reading without contortion even if the detector is carried at the belt.
Technical Data
Detection Principles | Electrochemical, Catalytic combustion sensor, Thermal conductivity, Infra-red sensor. |
---|---|
Alarms (Visual) ( Audible) |
Bright 360 LEDs 103 dB |
Data Logger | |
Dimensions(WxHxD) | 90 x 100 x 55mm |
Weight | 280g |
Power Supply | 2AA batteries NiMh battery pack |
Temperature Range | |
Operation Time | up to 24 hours |
Approvals | EEx ia d IIC T3/T4 |
Enclosure | IP 67 |
We are a widely respected Manufacturer and Supplier of Beagle Residential Gas Leakage Detectors in Mumbai. The Beagle Residential Gas Leakage Detectors, offered by us, are available in various models and have numerous attractive features that enhance their efficiency and make them widely popular among the clients.
Features
Type Explanation
Technical Data
Model | NV-100C | NV-100H | NV-100D | NV-100S |
---|---|---|---|---|
Detection Principle | Catalytic combustion | Hot-Wire Semiconductor | Controlled Potential Electrolysis | Galvanic Cell |
Gas Detected | Combustible gas ( L.PG, Methane, .etc.) | Combustible gas ( L.PG, Methane, .etc.) | Toxic gas/ Semiconductor manufacturing gas | Oxygen (deficiency/leakage) |
Detection Range | 0-100%LEL | As per specification | As per specification | 0-25vol% (deficiency) 0-50vol% (leakage) |
Concentration Indicator | LCD bar-graph meter with backlight | LCD bar-graph meter with backlight | LCD bar-graph meter with backlight | LCD bar-graph meter with backlight |
Alarm Accuracy | ±25% of an alarm set value | ±25% of an alarm set value | ±30% of an alarm set value | ±1.0vol% of an alarm set value (conferms to JIS T 8201) |
Operating Temperature Range | 0oC to 40oC | 0oC to 40oC | 0oC to 40oC | 0oC to 40oC |
Power Source/Power Consumption | 100-240V AC, 50/60Hz (standard), 24V DC (option); Diffusion type: 12VA/17VA (with the backup power source), Suction type: 4VA per unit to be added | 100-240V AC, 50/60Hz (standard), 24V DC (option); Diffusion type: 12VA/17VA (with the backup power source), Suction type: 4VA per unit to be added | 100-240V AC, 50/60Hz (standard), 24V DC (option); Diffusion type: 12VA/17VA (with the backup power source), Suction type: 4VA per unit to be added | 100-240V AC, 50/60Hz (standard), 24V DC (option); Diffusion type: 12VA/17VA (with the backup power source), Suction type: 4VA per unit to be added |
Alarm Indication | Ist stage: Red lamp for Ist stage alarm flashing, 2nd stage: Red lamps for Ist and 2nd stage alarms flashing | Ist stage: Red lamp for Ist stage alarm flashing, 2nd stage: Red lamps for Ist and 2nd stage alarms flashing | Ist stage: Red lamp for Ist stage alarm flashing, 2nd stage: Red lamps for Ist and 2nd stage alarms flashing | Ist stage: Red lamp for Ist stage alarm flashing, 2nd stage: Red lamps for Ist and 2nd stage alarms flashing |
Trouble Indication | Power source lamp lights up in orange | Power source lamp lights up in orange | Power source lamp lights up in orange | Power source lamp lights up in orange |
External Output | Alarm output terminal - 1st alarm (1c no-voltage contact), 2nd alarm (1c no-voltage contact,. Trouble alarm (1c no-voltage contact). Buzzer(1a no-voltage contact); Analog oulput : 4- 20mA; Contact capacity: 2A@100V AC (resistance load) | Alarm output terminal - 1st alarm (1c no-voltage contact), 2nd alarm (1c no-voltage contact,. Trouble alarm (1c no-voltage contact). Buzzer(1a no-voltage contact); Analog oulput : 4- 20mA; Contact capacity: 2A@100V AC (resistance load) | Alarm output terminal - 1st alarm (1c no-voltage contact), 2nd alarm (1c no-voltage contact,. Trouble alarm (1c no-voltage contact). Buzzer(1a no-voltage contact); Analog oulput : 4- 20mA; Contact capacity: 2A@100V AC (resistance load) | Alarm output terminal - 1st alarm (1c no-voltage contact), 2nd alarm (1c no-voltage contact,. Trouble alarm (1c no-voltage contact). Buzzer(1a no-voltage contact); Analog oulput : 4- 20mA; Contact capacity: 2A@100V AC (resistance load) |
Dimensions | Without backup power source : W 113.x H2O4 x D71.5mm, approx. 1.5kg With backup power source : W113xH234xD110mm, Approx. 3kg |
Without backup power source : W 113.x H2O4 x D71.5mm, approx. 1.5kg With backup power source : W113xH234xD110mm, Approx. 3kg |
Without backup power source : W 113.x H2O4 x D71.5mm, approx. 1.5kg With backup power source : W113xH234xD110mm, Approx. 3kg |
Without backup power source : W 113.x H2O4 x D71.5mm, approx. 1.5kg With backup power source : W113xH234xD110mm, Approx. 3kg |
Technical Data
Detection Principles | Electrochemical, Catalytic combustion sensor, Thermal conductivity, Infra-red sensor. |
---|---|
Alarms (Visual) ( Audible) | Big red LED 90 dB |
Data Logger | Optional |
Dimensions(WxHxD) | 90 x 210 x 60mm |
Weight | 660 - 770g |
Power Supply | Metalhydride, rechargeable, quickly replaceable |
Temperature Range | -20º to +50º c |
Operation Time | 8 - 20 hours |
Approvals | EEx ib d IIC T5 |
Enclosure | IP 54 |
Features
Specifications
Model | XP- 702IIZ-B | XP - 702IIZ-A | XP - 702IIZ-F |
Gas Detected | One type of combustible gas (e.g., city gas, LPG) | Two types of combustible gas (selectable) | CFC substitutes and combustible gas (selectable) |
Detection Principle | Hot wire semiconductor | ||
Minimum Detectable Leak Rate | City gas, LPG, etc. : 3.3x10-6 Pa m3/SCFCs : Leakage of 12.4 g/year (R-407C) or 11.2 g/year (R-410A) | ||
Minimum Detectable Concentration | City gas, LPG, etc. : 10ppmCFCs : 30ppm | ||
Response Time | 3s or less (not including CFCs) | ||
Detection Indication | Intermittent buzzer and fl ashing lamp | ||
Power Source | 3xAA alkaline dry cells | ||
Battery Life | Up to 18 hours (by alkaline dry cells) at constant temperature and humidity | ||
Explosion-Proof Structure | Sensor: Pressurization, Other parts: Intrinsic safety | ||
Operating Temperature | -20 to 500C | ||
Dimensions | W60 x H140 x D40mm (excluding protrusions) | ||
Weight | Approx. 260g (excluding batteries) | ||
Standard Accessories | Probe with fi lter/moisture trap, Check gas, Standard attachment, 3xAA alkaline dry cells, Hand strap, Spare fi lters | ||
Optional Accessories | Probe for testing roadway surfaces, Telescopic gas probe, Earphones, etc. |