Company Information
Ask for more detail from the seller
Contact SupplierThe AVR controller is a state of the art microcontroller technology based voltage regulating relay product form Proton. The AVR controller has the complete operating logic of the processes preprogrammed.
Â
The operating mode can be selected using TEST or NORMAL Mode front panel Switch:Â
> In this mode the AVR is operational. If PT input voltage is less than PT set point voltage minus hysteresis, then HIGH LED glow & there is a pulse of LOWER RELAY as per user setting pulse time & delay between two pulses & it clears if PT input voltage is greater than or equal to PT set pointÂ
> If PT input voltage is greater than PT set point voltage plus hysteresis, then LOW LED glow & there is a pulse of RAISE RELAY as per user setting pulse time & delay between two pulses, & it clears if PT input voltage is less than or equal to PT set point .Â
> If PT input voltage is less than UV set point then UV relay on & UV LED glow & it clears if PT input voltage is greater than or equal to UV set point plus hysteresis.Â
> In TEST mode there is one potentiometer at front side of unit, it is independent of PT supply.Â
As per Potentiometer value voltage , Test Low & Test High LED glows as per PT voltage set point..
> To enter settings mode press set key and then press increment key for enter the correct password.Â
> The password value can be set by using INC or DEC key & then press ENT key.Â
> Press set key to move to next parameter. To edit parameter press increment/decrement keysÂ
> To save and exit SET mode press ENT key.Â
> If no key is pressed then controller automatically goes to initial Display normal mode.
> The factory set password is 11.
Â
Â