No. of OutputsMaximum 4 parallel independent outputs can be provided for single input.
Supply90 -260 VAC, 50/60Hz or 24VDC @ 200mA
IsolationInput and Output are optically isolated for DC and frequency inputs and galvanically isolated for the AC inputs.
AccuracyFor Thermocouple and RTD Input, the calibration of output is done for the best straight line fit to give accuracy of /- 0.5% of the range. For other input the linearity depends on the input signal, where output accuracy is absolute to the input.
Output(4-20) mA, (0-20) mA, (0-1) VDC, (0-5) VDC, (0-10) VDC, Frequency (0-1)KHz, (0-5)KHz, (0-10)KHz etc. proportional to the specified input range. For current output, RL (max.) = 500 Ohms. For voltage output, RL (min) = 10K Ohms.
CalibrationOn site calibration facility through ZERO and SPAN presets accessible to the user.
Size65(W) x 80(H) x 125(D) mm.
RangeUser may specify the required temperature range (for RTD or T/C input). For other inputs the required calibration range can be specified.
DesignBased on F/V and V/F linear circuit.
No. of OutputsMaximum 4 parallel independent outputs can be provided for single input.
AccuracyFor Thermocouple and RTD Input, the calibration of output is done for the best straight line fit to give accuracy of /- 0.5% of the range. For other input the linearity depends on the input signal, where output accuracy is absolute to the input.
Input typesRTD (Pt-100) / 2 or 3 wire or Thermocouple (J/K/ Types – type to be specified) or mV, mA input or Load cell, pressure sensor, pH/ORP sensor etc. generating DC current or voltage. AC input - Current (through external CT) (0-1)A or (0-5)A or Voltage (0-11
Supply90 -260 VAC, 50/60Hz or 24VDC @ 200mA
MountingDIN rail mounting ABS enclosure.
IsolationInput and Output are optically isolated for DC and frequency inputs and galvanically isolated for the AC inputs.
Isolation VoltageGreater than 2.5KV.
Interested in this product? Ask for more details & Latest Price from seller