Our Products
We offer the best product range of Bus Duct Current Transformer, Medium Voltage Indoor Resin Cast Current Transformer, Medium Voltage Outdoor Oil Filled Combined CTVT Current Transformer and Medium Voltage Outdoor Oil Filled Current Transformer.
Technical Specification
| Application | Outdoor |
| Highest Voltage for Equipment (kV) | Up to 36 kV |
| Rated Insulation Level (kV) | Up to 36/70/170kVp |
| Rated Frequency (Hz) | 50-400Hz |
| CT Specifications | |
| Type | Wound Primary Type |
| Rated Primary Current (A) | Up to 3000A |
| Rated Secondary Current(A) | 5A or 1A |
| Accuracy class | 0.1, 0.2s, 0.2, 0.5s, 0.5, 1, 3, 5 |
| Instrument Safety Factor | <=5 (Depending on Accuracy Class) |
| Rated Burden (VA) | Up to 30VA (As Per Requirement) |
| Accuracy Class of Protection Core | 5P to 15P |
| Accuracy Limited Factor(ALF) | 5 to 30 |
| Special Protection(PS/PX) | VK=> ....v(As Per Requirement) |
| Short Time Thermal Current(STC) | >Up to 40 kA at 0.5sec 1, sec or 3 sec |
| Number of Cores | 1-2-3-4-5 |
| VT Specifications | |
| Rated Primary Voltage(V) | Up to 33kV |
| Rated Secondary Voltage(V) | 110V/RT3, 110V/3, 110V (As Per Requirement) |
| Accuracy class | 0.1, 0.2, 0.5, 1, 3 |
| Rated Burden (VA) | Up to 500VA |
| Accuracy Class of Protection Core | 3P to 6P |
| Number of Windings | 1-2-3-4-5 |
| Voltage Factor | 1.2 Continuous/1.5 for 30 sec, 1.9 for 8 hours |
| Type of Earthing | One End Earthed Type (E-N)/ UnEarthed Type (U-N) |
| Class of insulation | Class A |
| Applicable Standards | IS,IEC,ANSI,BS,etc. |