We offer the Power+N range of Neutral Grounding Resistor (NGR) Panels up to 66 KV. Ngr’s are used to connect the neutral phase and the earth to limit the earth fault current to a safe value....
View More Details
Send Enquiry

Company Information

  • Member Since 15 Years
  • Nature of Business Retailer
  • Year of Establishment 1969

Ask for more detail from the seller

Contact Supplier

Product Details no_img_icon

We offer the Power+N range of Neutral Grounding Resistor (NGR) Panels up to 66 KV. Ngr’s are used to connect the neutral phase and the earth to limit the earth fault current to a safe value thereby protecting the transformer, generator system. The Typical operation conditions are A No Earth Fault: Continuous current (5 % to 10 % of full load current) may pass through the resistor due to system unbalance or Earth Fault Condition where restricted fault current passes through the resistor protecting the system till automatic protection takes place.

Power+N Neutral Grounding Resistor Panels upto 66 KV

Purpose: Neutral Grounding Resistor is connected between the neutral & the earth so that it will limit the earth fault current to a safe value [Normally full load current of the generator, transformer, etc. thereby protecting the transformer, generator system].
Typical operation conditions:
1. No Earth Fault: Continuous current (5 % to 10 % of full load current) may pass through the resistor due to system unbalance.
2. Earth Fault Condition: Restricted fault current passes through the resistor protecting the system till automatic protection takes place. The earth pressure (Rated Voltage) is absorbed by the resistor protecting the winding etc.

Salient Design features:

Enclosure: For outdoors application enclosure designed to give degree of protection of IP 33 is normally used. Enclosure upto IP 65 protection are offered. Enclosure material can be Mild Steel, Aluminium or Stainless Steel. Painting / Galvanizing or Hot Dip Galvanizing or Powder Coating is offered as per requirement. Safety screen enclosure is provided if required. For continuous rating enclosure protection is not above IP 43.

Material of Resistor Element: A Neutral Grounding Resistor is a very simple yet technical equipment that is an absolute requirement depending on the design of the installation. Our NGR panels are fitted with resistor elements made from stainless steel or cast iron or CU-NI or NI-CR or any other resistance material as per requirement. From our experience, formed stainless steel elements are best and economical for NGRS.

Construction: NGR include resistor assembly, plus required insulators, internal connections and hardware.

Options/Accesories: Few of the following are usually incorporated. Current Transformers, Potentials Transformers, Grounding Transformers, Two bushing, Elevating Stands, Manual/ Electrical operated/ Motorized Isolator, Earth Leakage Relay, Lightning Arrestors, Auxiliary Control Wiring Terminal Box with Cable Glands, Termination Kit, Stand Off Insulator, Space Heater with Thermostat Control are also offered.

Cabling/ Termination: Suitable arrangement is provided for termination of cable, flats or bus duct as per requirement. Incase of XLPE cable terminal box with suitable clearance and undrilled removable gland plate is provided.

Typical Specifications:

Rated Voltage: In an NGR this voltage means value of line to neutral voltage (ie System Voltage divided by 1.732)

Rated Current: This is the value of initial current that will flow through resistor when it is cold. Normally rated current value is same as full load current.

Duty rating or Time Rating:Also referred to as Duty rating, is length of time for which NGR must withstand rated voltage.

Short Time Rating: This is dependent on the design parameters of the protection system, normally it is 10 or 30 or 60 seconds. When a fault is immediately cleared and system made healthy then chances of fault repetition should be considered. 30 sec is the typical rating recomemded b y IS-304.

Continuous Rating: This is typically 10 % of full load current. For a healthy systems the NGR can be designed for a continuous rating of 5% to 10 % of full load current.

Temperature Rise Allowed: Normally Temp. Rise is restricted to 375 deg.c ie as per BS 587. It can be 760 deg.c. As per IEEE-32. We can offer NGR of any other temp. Rise as per the design requirements.



Company Details close-icon

New India Electricals Ltd specializes in providing innovative engineering solutions for hundreds of customers worldwide. Pioneered by Shri Narendra M Desai in 1969, today we are amplifying the breadth of product range and geographic footprint in the industrial sector.
At New India Electricals Ltd, our aim is to provide a comprehensive range of highly reliable systems and equipment for power, motor and pumping applications. With the highly qualified engineering and manufacturing capabilities, we have provided a strong local as well as global presence to our customers in over 25 Indian states as well as within 45+ other countries spanning multiple continents.
  • Nature of Business Manufacturer / Exporter / Supplier / Retailer
  • Number of Employees 150 - 200
  • Year of Establishment 1969
Tell us your Buy Requirement to Get Instant Response
Tell us what you need?

Looking for neutral grounding resistor panel?

Quantity
Seller Contact Details
  • Seller New India Electricals Ltd.
  • Address Jc Nagar, Bangalore, Karnataka

Find similar products

View all products in Resistors
Waiting for permission
To search by voice, go to your browser settings and allow access to microphone

Allow microphone access to search with voice