Contact SupplierWe are expert in the designing and developing of Solar Differential Controller with perfection. Solar Differential Controller is precisely designed in line with the established quality parameters of the industry. Longer service life, efficient performance and low operating cost are the prominent attributes of Solar Differential Controller. General Descriptions
Faults
| Fault on the display | S1 | S2 | Voice alarm |
| F01 | O.K. | Short circuit | Yes |
| F02 | O.K. | Cable cut off | Yes |
| F03 | Short circuit | O.K. | Yes |
| F04 | Cable cut off | O.K. | Yes |
| F05 | Short circuit | Short circuit | Yes |
| F06 | Cable cut off | Short circuit | Yes |
| F07 | Short circuit | Cable cut off | Yes |
| F08 | Cable cut off | Cable cut off | Yes |
| F09 | Very high temp. difference due to circulator stuck or no loop flow | Yes | |
| Ζ | Slide switch for turning on/off the controller and manual power output |
|---|---|
| Γ | Button sol-blr-dif. Successive pressing appears on the display the temperature of the solar panel, the temperature of the storage tank and their differences. Wherever you leave the status the display shows the corresponding value. |
| Α | Prg-set button. Five seconds pressing enters the first parameter of the controller. With the same button you enter the next parameter. Pressing B or Γ button you change the value and you fix it by pressing the Α button. The display flashes twice and returns to the operation status. |
| Parameters | Description | RangeoC | DefaultoC |
|---|---|---|---|
| E0 | S1-S2≥E0 relay on | 2-50 | 7 |
| E1 | S1-S2≤ E1 relay off | 0-49 | 0 |
| E2 | S1≥ additional condition, relay on | 10-80 | 25 |
| E3 | S2≤ additional condition, relay on | 0-90 | 90 |
| E4 | S1-S2≥E4 after 30 minutes and voice alarm activated. F09 display fault | 15-60 | 30 |
| E5 | Correction of S1 temperature due to very long cable more than 30m. | -5-+5 | 0 |
| E6 | Correction of S1 temperature due to very long cable more than 30m. | -5-+5 | 0 |
| E7 | Freeze protection: relay on when S1-S2≤2 0C and relay off when S1≥6oC E7=1 freeze protection active and E7=0 disactive | 0/1 | 1 |
| E8 | Restoration of the initial values | DEF | DEF |
| Note : S1=Solar Temperature, S2=Boiler Temperature | |||